Supply the protection unit always and continually with voltage in the range
of 110...220Vac/dc. Supply terminals: r+("+") and r2-("-").
Front View
Indicates the instantaneous currents by phase, set parameters, frequency,

LCD DISPLAY

LED RUN
LED PICK UP
LED LTD
LED STD
LED INST
LED PAL
RESET key
MODE key
ENT key
 and keys
Start Screen
When first turned on, the protection unit presents the screen below on the display for
approximately 2 seconds:
ACB OCR-II
Vx.x
After this period, the standard screen is presented, where the values of the instantaneous
currents by phase are read:
R: * * * *
T: * * * *
AttentIon!
In the case of instantaneous current being less than 5% of the maximum
nominal current (In max.) of the circuit breaker, "****" will be shown on the
display.
Indication/Signaling of the occurrence of Faults
In case of tripping through overload or a short circuit, the protection unit indicates the fault
through the LCD display, and signals it through the LEDs in the front and alarm contacts.
faults occurred and information of self-diagnosis of the protection unit.
The LED flashes intermittently in normal operation.
Signals beginning of trip timing.
Signals tripping through overload (L function).
Signals tripping through timed short circuit (S function).
Signals tripping through instantaneous short circuit (I function).
To reset the alarm contacts and the LEDs of signaling of faults.
To return to the previous menu.
S: * * * *
N: * * * *
English
Signals pre-alarm.
To access the menus.
To advance / go back.
open Circuit Breaker
ABW | 31