Product description
3.3.2 Non-testable sensors
When DIP switches 1 and 5 are set as shown, the sensors are
not tested. The non-testable sensors include all other sensor
types not mentioned in the preceding subsection. On non-
testable sensors the sensor output signal is "HIGH "in the
active state. The following safety rules apply to the use of non-
testable sensors:
On power-up all muting sensors must be inactive, otherwise
the muting indicator lamp will flash at 2 Hz (twice per
second).
With continuous muting concurrence monitoring of the
muting sensors must be selected.
The cables between the MSM and the sensors must be laid
appropriately to avoid crossed connections between the
cables of the sensors of one pair.
Output
Muting condition
Muting sensor
HIGH
Met
LOW
Not met
GB
Section 3