S19-2010 Series
1

Mount Valve on the Wall

A
Use (3) 1/4" screws to mount the valve
assembly on the wall.
3-3/4"
(95)
2

Connect Outlet Lines

A
Install 1/2" compression fitting, hoses, or
pipe fittings into the valve outlets as shown
in the illustration.
B
Install unions or union-function equivalent
fittings (hoses with swivel connectors) in the
outlet lines to facilitate valve removal.
C
An optional 3/8" compression fitting is
provided for faucet outlet connection.
WARNING Do not install a 3/8" compression fitting on the eyewash outlet.
This will restrict the flow. The eyewash outlet line must use a
1/2" compression fitting to ensure proper flow.
WARNING Do not connect the faucet outlet to the eyewash unit.
This may cause scalding.
4
2-1/16"
(52)
1/20/2020
1"
1-1/8"
(25)
Ø 5/16"
3x
1-1/4"
(32)
4-5/16"
(110)
6-1/4"
(159)
(29)
1-1/8"
(29)
2"
(51)
1"
(25)
To Eyewash
Bradley • 215-1873 Rev. B: ECO 20-09-002
Installation
(mm)
To Faucet

Publicidad

Tabla de contenido
loading