Troubleshooting

Malfunction
Incorrect flushes (too soon, too late,
unwanted)
Water is running continuously into
the urinal ceramic appliance.
Flushing out of the urinal ceramic
appliance is inadequate.
Flush volume is inadequate.
Battery warning level 1
(4 short signal tones upon entering
the detection range)
Battery warning level 2
(No flush actuation, 2 short signal
tones every 30 seconds)
Battery warning level 3
(No flush actuation, no signal tone)
18014401623384843-1 © 09-2018
966.934.00.0 (02)
Cause
Detection distance
not set correctly
IR window is dirty or
wet
IR window scratched
Software fault
Technical fault
Flush time set incor-
rectly
Basket filter in
solenoid valve
clogged
Batteries dead
Rechargeable battery
empty
Action
▶ Optimise the detection
distance.
▶ Clean or dry the IR window.
▶ Contact a skilled person.
▶ Restart the urinal flush
control.
▶ Contact a skilled person.
▶ Set flush time.
▶ Clean the basket filter.
▶ Replace the batteries.
▶ Charge the rechargeable
battery of the self-sustaining
power supply.