Troubleshooting

Malfunction
Incorrect flushes (too soon, too late,
unwanted)
Water is running continuously into
the urinal ceramic appliance.
Flushing out of the urinal ceramic
appliance is inadequate.
Flush volume is inadequate.
No flush actuation
9007202368641931-1 © 07-2018
966.933.00.0 (02)
Cause
Detection distance
not set correctly
IR window is dirty or
wet
IR window scratched
Software fault
Technical fault
Flush time set
incorrectly
Basket filter in
solenoid valve
clogged
Network failure
Action
▶ Optimise the detection
distance.
▶ Clean or dry the IR window.
▶ Contact a skilled person.
▶ Restart the urinal flush
control.
▶ Contact a skilled person.
▶ Set flush time.
▶ Clean the basket filter.
▶ Check the power supply.