EtherNet/IP configuration
This web page is used to configure all the parameters relevant to the EtherNet/IP protocol standard.
Fig. 6
Real Time Ethernet Protocol Configuration - EtherNet/IP
Object
Description
Configuration of the static IP address if a DHCP server is not used. EtherNet/IP is not
IP Address
allowed to share the IP address with a CIM 500 webserver.
Subnet Mask
Configuration of the subnet mask if a DHCP server is not used.
Gateway
Configuration of the gateway address if a DHCP server is not used.
The CIM 500 module can be configured to automatically obtain its EtherNet/IP network
Use DHCP
settings from a DHCP
For enabling of a 5 seconds communication watchdog timer. Only active for pump or
booster products.
Communication
Unchecked: Watchdog is disabled (default)
Watchdog
Checked: Watchdog is enabled, time-out 5 seconds.
Watchdog action: The pump or the booster is set to local mode.
The module can be put in product simulation mode to generate realistic simulated
values of all the EtherNet/IP input data. It will thus be possible to connect a EtherNet/IP
master to a module fitted in a CIU or an E-box without installing this device in a real
Grundfos product
industrial process system. In an office environment, it can then be verified that
simulation
communication
master application program (for example PLC program) before installing the device.
To enable product simulation, select a product type from the dropdown list.
To terminate product simulation, select "No Simulation".
server,
if available on the network. Default: No use of DHCP.
works,
and data is received and handled correctly by the EtherNet/IP
189