Cim 500 Ethernet Module; Installation; Security - Grundfos CIM 500 Instrucciones De Instalación Y Funcionamiento

Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 49

2.2 CIM 500 Ethernet module

2
1
3
5
4
Fig. 1
CIM 500 Ethernet module
Pos.
Designation
1
ETH1
2
ETH2
3
DATA1
4
LINK1
5
DATA2
6
LINK2
7
LED1
8
LED2
9
SW1
6
9
7
8
6
Description
Industrial Ethernet RJ45
connector 1
Industrial Ethernet RJ45
connector 2
Data activity LED for
RJ45 connector 1
Link LED for RJ45
connector 1
Data activity LED for
RJ45 connector 2
Link LED for RJ45
connector 2
Red and green status
LED for the selected
Ethernet protocol
Red and green LED for
internal communication
between CIM 500 and
the Grundfos product
Rotary switch for
selection of Industrial
Ethernet protocol

3. Installation

WARNING
Electric shock
Death or serious personal injury
- Only connect CIM 500 to SELV or
SELV-E circuits.
Fig. 2
QR code for the CIU quick guide

3.1 Security

Grundfos connected products must be behind a
firewall or connected to a private network.
If a firewall or private network is not in place, the
Grundfos product may be subject to a cyber-security
risk and becomes vulnerable to an attack or
compromise.
Follow the highly recommended configuration
requirements below. If in doubt, consult an IT
Infrastructure Specialist.
3.1.1 CIM 500
CIM 500 is a traditional network-connected device
and must be placed on a private network behind a
firewall. It must not be connected directly to the
Internet. Also, no TCP/IP ports must be forwarded to
the product. If you need remote access to the device,
you must use technologies such as Virtual Private
Networks (VPNs) to ensure a secured connection.
Consider contacting an IT Infrastructure Specialist to
establish such a solution.
For CIM 500 in mode 4, GRM IP (Grundfos Remote
Management) the firewall must accept connections
initialised by the Grundfos product to the Internet
only (outgoing connections).
Grundfos
1
Firewall
2
device
Fig. 3
Secure connectivity for CIM 500
Internet
3

Publicidad

Tabla de contenido
loading