External control input of the speed stage - Current signal: Position [S3]
100 %
Converter
frequency
~30 %
0
External control input of the speed stage - Voltage signal: Position [S4]
100 %
Converter
frequency
~30 %
0
External setpoint input of control with a sensor (pressure, temperature, delivery rate, etc.)
100 %
Setpoint
in %
of the sensor's
measurement
range
0
50
External signal 4-20 mA
Area where the converter
deactivates
Safety area
6
10
Current input (mA)
External signal 2-10
V
 
Area where the converter
deactivates
Safety area
3
5
Voltage input (V)
Setpoint signal 4-20 mA: Position [S5]
Area where the converter
deactivates
Safety area
2
4
Current input (mA)
100 %
Converter
frequency
~30 %
20
0
100 %
Converter
frequency
~30 %
0
10
100 %
Setpoint
in % of
the sensor's
measurement
range
20
0
External signal 0-20 mA
Area where the converter
deactivates
Safety area
2
4
Current input (mA)
External signal 0-10
V
 
Area where the converter
deactivates
Safety area
1
2
Voltage input (V)
Setpoint signal 2-10
V: Position [S6]
 
Area where the converter
deactivates
Safety area
1
2
Voltage input (V)
WILO SE 04/2020
20
10
10