address
ıtem
40200
rELAY 1 LOGIc
40202
rELAY 1 LOW VALUE
40204
rELAY 1 HIGH VALUE
40206
rELAY 1 dELAY tIME
40208
rELAY 2 LOGIc
40210
rELAY 2 LOW VALUE
40212
rELAY 2 HIGH VALUE
40214
rELAY 2 dELAY tIME
address
ıtem
40400
tYPE_UnIt
dIsPLAY
40402
dEcIMALs
40404
IntErVAL
40406
FILtEr
40408
dELAY
system Value reading registers (read Only)
Description
relay 1 logic. 0=LOW 1=HIGH
Low level value for relay 1.
MAIn_VALUE_dEcIMALs register
shows its decimal. (40104)
MAIn_VALUE_tYPE_UnIt_cOdE
register shows type/unit of the value.
(40106)
High level value for relay 1.
MAIn_VALUE_dEcIMALs register
shows its decimal. (40104)
MAIn_VALUE_tYPE_UnIt_cOdE
register shows type/unit of the value.
(40106)
delay time for relay 1 in seconds
relay 2 logic. 0=LOW 1=HIGH
Low level value for relay 2.
MAIn_VALUE_dEcIMALs register
shows its decimal. (40104)
MAIn_VALUE_tYPE_UnIt_cOdE
register shows type/unit of the value.
(40106)
High level value for relay 2.
MAIn_VALUE_dEcIMALs register
shows its decimal. (40104)
MAIn_VALUE_tYPE_UnIt_cOdE
register shows type/unit of the value.
(40106)
delay time for relay 2 in seconds
Description
It defines which type of measurement
will be made with which unit in main
value of the device. (table 1)
It defines how decimal the main value
will be shown on Lcd display of device.
(table 2)
number of measurements to be taken
per second.
Filtering of measured values. 0=no
filter, 16=maximum filtering.
Delay time of fault relay in seconds.
size
valid
type
(byte)
value
Long
4
0 or 1
Long
4
-
Long
4
-
Long
4
0..16
Long
4
0 or 1
Long
4
-
Long
4
-
Long
4
0..16
size
valid
type
(byte)
value
Long
4
1..11
Long
4
0..3
Long
4
1..8
Long
4
0..16
Long
4
0..15
Orion Echo Ultrasonic Level Probe
Unit
-
M, cm, inch
Feet,M
,
3
Liter, Us
Gallon
M, cm, inch
Feet, M
,
3
Liter, Us
Gallon
second
-
M, cm, inch
Feet, M
,
3
Liter, Us
Gallon
M, cm, inch
Feet, M
,
3
Liter, Us
Gallon
second
Unit
-
measurement/
second
-
second
33