Command #11 Read Unique Identifier Associated With Tag
request data bytes
response data bytes
response codes
note
command #12 read Message
request data bytes
response data bytes
response codes
command #13 read tag descriptor date
request data bytes
response data bytes
response codes
Command #14 Read PV Sensor Information
request data bytes
response data bytes
response codes
Command #15 Read Output Information
request data bytes
response data bytes
38
Orion Echo Ultrasonic Level Probe
#0 to #5 - tag (6 byte Packed-AscII = 8 char.)
#0 – 254 (fixed)
#1 - Manufacturer Id = 255 (general)
#2 - Manufacturer device type = 32 for Ultrasonic Transducer
#3 - number of Preambles
#4 - Univ cmd rev
#5 - trans spec rev
#6 - Soft Rev (37 for 3.7)
#7 - Hard rev (12 for 1.2)
#8 - Flags
#9 to #11 - device Id number (24-bit unsigned int)
#0 - No Command-Specific Errors
response only if tag corresponds
- Only valid for broadcast Frames
none
#0 to #23 - Message (24 byte Packed-AscII = 32 character)
#0 - No Command-Specific Errors
none
#0 to #5 - tag (Packed-AscII = 8 char.)
#6 to #17 - descriptor (Packed-AscII = 16 char.)
#18 to #20 - date [dd.mm.yy]
#0 - No Command-Specific Errors
none
#0 to #2 - P.V. sensor serial number
#3 - P.V. sensor Units code
#4 to #7 - P.V. Upper sensor Limit
#8 to #11 - P.V. Lower sensor Limit
#12 to #15 - P.V. Minimum span
#0 - No Command-Specific Errors
none
#0 - Alarm select code
#1 - P.V. Transfer Function Code (Not used , 0)
#2 - P.V. range Units code
#3 to #6 - P.V. Upper range Value
#7 to #10 - P.V. Lower range Value
#11 to #14 - P.V. Damping Value (fixed 10)
#15 - Write Protect code (not used , 0)
#16 - Private Label distributor code (not used , 0)