Error
Cause
Communication error to
CAN-IN1 object receives faulty data or
CAN-IN1 with event or
communication is interrupted
time control
BUS-OFF
Controller has received too many
incorrect telegrams via the system
(many communication
bus and has been disconnected
faults occurred)
CAN Time-Out
For remote parameter setting via
system bus (C0370):
(configurable in C0126)
Slave does not answer.
Communication monitoring time
exceeded.
For operation with application I/O:
Faulty parameter setting of parameter
set changeover
For operation with module in FIF:
Internal fault
Function module
CAN controller sets "Warning" or "BUS
system bus (CAN) on
OFF"
FIF has set "Warning"
or "BUS-OFF"
(configurable in C0126)
Communication fault
Participant does respond or is not
during remote
available
parameter setting via
system bus (C0370)
(configurable in C0126)
For operation with application I/O:
Faulty parameter setting of parameter
set changeover
External fault
A digital input assigned to the
(TRIP-SET)
TRIP-Set function has been activated.
Communication abort
Various
between keypad and
basic device
E82ZMV fan module
Fan module is defect
(only 8200 motec
3 ... 7,5 kW)
3 ... 7,5 kW)
TRIP or warning
Fan module is not connected
configurable under
C0608
Internal fault
Remedy
Plug-in connection - bus module
Check FIF
Check transmitter
Increase monitoring time under C0357/3
if necessary
Check whether bus terminator available
Check screen contact of the cables
Check PE connection
Check bus load, if necessary, reduce the
baud rate
Check system bus wiring
Check system bus configuration
In all parameter sets the signal "parameter
set changeover" (C0410/13, C0410/14)
must be combined with the same source
Contact Lenze
Check whether bus terminator available
Check screen contact of the cables
Check PE connection
Check bus load, if necessary, reduce the
baud rate
Check whether bus terminator available
Check screen contact of the cables
Check PE connection
Check bus load, if necessary, reduce the
baud rate
In all parameter sets the signal "parameter
set changeover" (C0410/13, C0410/14)
must be combined with the same source
Check external encoder
Contact Lenze
Replace fan module
Connect fan module
Check wiring
Contact Lenze