Installation Procedures
Apple refrigerant oil
Pipe size
Model
40VL005~018B-7E-QEE
INSTALLATION OF WATER DRAINAGE PIPE
(1) Install the water drainage pipe
• Pipe diameter should be equal or larger than that of the unit piping.(pipe of polyethylene; size: 20mm; O.D:26mm)
• Drain pipe should be short, with a downward slope of at least 1/100 to prevent air bag from forming.
• If downward slope can't be created, take other measures to lift it up.
• Please install the drain hose towards a downward slope without fail.
• Please don't fix the drainage as shown below.
• Please pour water in the drain pan of the indoor unit and confirm that drainage is being drained to the outdoor.
• In case that the attached drain hose is in a room, please heat insulate it without fail.
It becomes
high midway.
Torque spanner
spanner
Piping joing
Flare nut
Gas pipe
012.7mm
The end is imm-
ersed in water
Medium size seal pad
(Cover the piping joint with seal pad.)
Clamp
Liquid pipe
Liquid pipe
0 6.35mm
It waves
The gap with the
ground is too small.
15
(accessory)
Insulator (accessory)
(For liquid pipe)
Insulator (accessory)
(For gas pipe)
gas pipe
Less than 5 cm
There is the bad
smell for ditch