Installation Procedures
Installation Space
Electric control
Enclosure
>100
Reserve 600x600 access hole
Installation of air-inlet grill
The angle of the air-inlet grill should be parallel
with that of air inlet direction, to avoid more noise
as shown in the figure on the right.
Installation of Duct Pipe of Indoor Units:
1. Installation of the ductwork:
With a square blast pipe, the bore shouldn't be less than the size of
the air outlet pipe.
2. Connection of return duct: Connect one side of the air return duct to
the air return port of the indoor unit with rivets and then the other
side to air return shutter, as shown in Fig. 1.
duct work attached to should be insulated to
prevent condensation.
Selection of fan outlet
This machine uses a DC motor, in which multi-range ESP adjustment is available. The factory default is standard ESP.
The ESP & Silent mode can be set according to the pipe resistance and the silence requirement. Setting ranges are as
follows:
Model
Ultra-silent
Grade
1
Operation:
When the 40VCW217FQEE wired controller is on, press the fan speed key & function key together for 5 seconds to get
into the ESP adjustment mode. When the grade number is flashing, press "up" and "down" to change, then press the
function key to set.
Remote control: Set temperature at 16°C and press "light" button on the remote controller 8 times in 10 seconds to hear
2 beeps. Then adjust the temperature to 17°C, press the button 'off ' to hear 1 beep.The grade 1(Ultra-silent )is set
successfully. If there is no action within two minutes, it will automatically exit the function setting.
Note:
This series is a low ESP duct. The remote control and all the above sets must be handled by 40VCW217FQEE after
asking our after-sales staff as per the installation condition at site. For more details, please check the 40VCW217FQEE
(upgraded) installation instructions manual.
Installation Mode
A
Please use a gradienter to make the levelness of unit within 5mm; If
end A is to drain water, ensure end B is slightly higher than the end A to
drainage; otherwise, ensure end A is slightly higher than end B.
>600
Correct
Silent
Standard ESP
2
Air In
Air Return
Shutter
default High ESP
3
4
8
4-M 10 hanging bolt
8-M 10 nut
8-
10 Washer
B
Wrong
Air In
Air Return
Pipe
Indoor Unit
Indoor Unit
Fig.1
Connection of oil return Pipe
Super high ESP
5