Electrical Wiring
Dipswitch Setting
• Indoor Units PCB
• In the following table, 1 represents ON and 0 represents OFF. Definition principles of code
switches:
• SWO1 is used to set the capabilities of the master and slave indoor units as well as
the indoor unit; SW03 is used to set the address of the indoor unit (combine original
communication address and address of centralized controller).
(A) Definition and description of SW01
(A) Definition and description of SW01
Address of
SW01_1
wire
SW01_2
controlled
SW01_3
indoor unit
(group
SW01_4
address)
SW01_5
Capability of
SW01_6
indoor unit
SW01_7
SW01_8
Note 1: A wired controller can connected to at most 16 ultrathin air-duct indoor units.
[1]
[2]
[3]
[4]
0
0
0
0
0
0
0
1
0
0
1
0
0
0
1
1
...
...
.. .
.. .
1
1
1
1
[5]
[6]
[7]
[8]
0
0
0
0
0
0
0
1
0
0
1
0
0
0
1
1
0
1
0
0
0
1
0
1
0
1
1
0
0
1
1
1
1
0
0
0
1
0
0
1
1
0
1
0
1
0
1
1
1
1
0
0
1
1
0
1
1
1
1
0
1
1
1
1
17
Address of wire controlled indoor unit (group
address)
0# (wire controlled master unit) (default)
1# (wire-controlled slave unit)
2# (wire-controlled slave unit)
3# (wire-controlled slave unit)
15# (wire-controlled slave unit)
Capability of indoor unit
0.6HP
0.8HP
1.0HP
1.2HP
1.5HP
1.7HP
2.0HP
2.5HP
3.0HP
3.2HP
4.0HP
5.0HP
6.0HP
8.0HP
10.0HP
15.0HP