General Information; Technical Information - Ingersoll Rand TS1A-13A Manual De Manejo Y Mantenimiento

Secador refrigerado
Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

8.1 TECHNICAL INFORMATION

General
Maximum ambient temperature _C (_F)
Minimum ambient temperature _C (_F)
Refrigerant type
Refrigerant oil
Maximum standard compressed air inlet pressure, barg (psig)
Control settings
Hot gas valve setting, barg (psig)
Thermal expansion valve superheat, _C (_F)
High refrigerant temperature switch setting _C
High pressure switch setting barg (psig)
Fan pressure switch setting on/off barg (psig)
Fan temp switch setting on/off _C (_F)
Low pressure switch setting barg (psig)
(1)(2)
Performance
Dew point temperature at rated conditions and flow, _C (_F)
Dew point temperature at rated conditions and flow, _C (_F)
Air Cooling System
Maximum ∆P across duct work, mm H
(1)
All standard 230v/1/50Hz, 230v/1/60Hz, 400v/3/50Hz and 380v/3/60Hz machines: 25_C ambient, 7 barg inlet, 35_C inlet, 35_C dew point
inlet.
(2)
All standard 230v/3/60Hz, 460v/3/60Hz and 575v/3/60Hz machines: 85_F ambient, 125 psig inlet, 100_F inlet, 100_F dew point inlet.
(3)
Always apply local electrical codes for sizing cables and fusing. In absence of local codes, the minimum cable size should always be calculated
on basis of maximum package full load x1.25.
(4)
High pressure options allow machines to operate at high pressure ratings. See machine specification data decal for pressure ratings for these
machines.
(5)
The low side refrigerant pressure is factory set at 5.38 – 5.66 barg (78 – 82 psig). It may need to be adjusted at the hot gas valve periodically due
to local ambient and seasonal changes to avoid dryer freeze–up. See section 11.4 "Routine Maintenance" for the adjustment procedure.
(6)
Evaporator superheat is factory set and should not require adjustment unless it is measured out of specification when the dryer is operating at
its nominal load, and the discharge air pressure dewpoint is high.
See "Routine Maintenance" for the adjustment procedure.
14
All manuals and user guides at all-guides.com

8.0 GENERAL INFORMATION

COMMON TECHNICAL DATA
(4)
(5)
(6)
(2)
(1)
O (in. H
O)
2
2
TS1A–13A
http://air.irco.com
46 (115)
2 (35)
R404A
ISO 32 Polyolester (POE)
12.1 (175)
5.03 – 5.66 (73 – 82)
3.3 – 5.0 (6.0 – 9.0)
115 (240)
29.3 (425)
16.5 / 13.1 (240 / 190)
99 / 82 (210 / 180)
2.8 (40)
3.8 (39)
3.0 (37.4)
1.0 (0.04)

Publicidad

Tabla de contenido
loading

Tabla de contenido