TS–11A 50/60Hz
KEY
A.
Electrical conduit connection
B.
Compressed air inlet
50Hz: 6" PN16–DN
60Hz: 6" ANSI
TS–11A
400v / 3 / 50Hz
1797 mm
460v / 3 / 60Hz
1668 mm
NOTES:
1.
Weight (approximate):
TS–11A: 740 kg (1628 lb)
2.
Refrigerant: R–404A
Tolerance on dimensions: 13mm (0.5") unless otherwise
3.
stated.
24
All manuals and user guides at all-guides.com
8.0 GENERAL INFORMATION
"X"
Fan Qty
2
2
C.
Compressed air discharge
50Hz: 6" PN16–DN
60Hz: 6" ANSI
D.
Condensate drain
50Hz: 1/4" BSP female
60Hz: 1/4" NPT female
4.
305mm (12") minimum electrical cable length allowance is
required between the electrical cable entry (A) and the mains
terminal block.
5.
Recommended clearance on all sides 1m(3ft) front panel with
starter door may require more as defined by local and national
electrical codes.
6.
External piping shall not exert any unresolved moments or
forces on it.
7.
There should be no plastic piping, not approved by IR, attached
to this unit or used for any lines downstream.
8.
Field installed ducting to and from the dryer can not add more
than 1.0mm (0.04) water air resistance.
TS1A–13A