User Setpoint Menu
#
NAME
1
Drain Valve Control
2
Drain Valve Open Time
3
Drain Valve Closed Time
4
MODBUS Control
5
MODBUS Address
6
PORO Control
The values displayed on the bar graphs are interpreted as follows:
Each light on the bar graph represents a number.
Add together the numbers represented by the illuminated lights to
get the displayed value.
Display Value = 8 + 2 + 1 = 11
The displayed value in the example above is 11.
All manuals and user guides at all-guides.com
9.0 OPERATING INSTRUCTIONS
Drain Valve Control Technique
Manual Drain Valve Open Time
Manual Drain Valve Closed Time
MODBUS Control State
MODBUS Local Address
PORO Control State
TS1A–13A
http://air.irco.com
DESCRIPTION
In the display shown above, the left side shows the setpoint function (in
this case a display value of 3 would indicate the Drain Valve Closed
Time). The right side shows the setpoint value (in this case a display
value of 22 would indicate 22 minutes). In summary, the Drain Valve
Closed Time is set to 22 minutes.
VALUES
1 = Manual
2 = Automatic
1 to 10 seconds
1 to 45 minutes
1 = Enabled
2 = Disabled
1 to 247
1 = Enabled
2 = Disabled
39