Ingersoll Rand TS1A-13A Manual De Manejo Y Mantenimiento página 24

Secador refrigerado
Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

TS–9A 50/60Hz
KEY
A.
Electrical conduit connection
B.
Compressed air inlet
50Hz: 4" PN16–DN
380v / 3 / 60Hz: 4" PN16–DN
All other 60Hz: 4" ANSI
TS–9A
380v / 3 / 60Hz
1666 mm
400v / 3 / 50Hz
1670 mm
460v / 3 / 60Hz
1668 mm
NOTES:
1.
Weight (approximate):
TS–9A: 595 kg (1309 lb)
2.
Refrigerant: R–404A
Tolerance on dimensions: 13mm (0.5") unless otherwise
3.
stated.
22
All manuals and user guides at all-guides.com
8.0 GENERAL INFORMATION
"X"
Fan Qty
3
2
2
C.
Compressed air discharge
50Hz: 4" PN16–DN
380v / 3 / 60Hz: 4" PN16–DN
All other 60Hz: 4" ANSI
D.
Condensate drain
50Hz: 1/4" BSP female
380v / 3 / 60Hz: 1/4" BSP female
All other 60Hz: 1/4" NPT female
4.
305mm (12") minimum electrical cable length allowance is
required between the electrical cable entry (A) and the mains
terminal block.
5.
Recommended clearance on all sides 1m(3ft) front panel with
starter door may require more as defined by local and national
electrical codes.
6.
External piping shall not exert any unresolved moments or
forces on it.
7.
There should be no plastic piping, not approved by IR, attached
to this unit or used for any lines downstream.
8.
Field installed ducting to and from the dryer can not add more
than 1.0mm (0.04) water air resistance.
TS1A–13A
http://air.irco.com

Publicidad

Tabla de contenido
loading

Tabla de contenido