Checking The Residual Current Device; Stop Button - Mennekes AMTRON Xtra Serie Manual De Instrucciones

Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 199

5.5.3 Checking the residual current device

Fig.: 14. Checking the residual current device
The residual current device can be tested for functionality
using the multifunction button without opening the hous-
ing.
f Insert a flat screwdriver with a blade width of 8 to
10 mm into the slot of the multifunction button.
f Turn the multifunction button 90° counterclockwise.
f Press the multifunction button for about two seconds
( > 5mm).
Is the residual current device functional?
The residual current device triggers.
9
The fault indicator on the LED info field flashes red.
9
f Switch the residual current device on again.
Î "5.5.2 Restarting residual current devices and miniature
circuit breakers"

5.6 Stop button

Only available for the equipment variants Premium E and
Xtra E.
Terminating charging and acknowledging faults
Fig.: 15. Terminating charging and acknowledging faults
Terminating a running charging process (only for devices
without authorization) and acknowledging faults.
f Press the stop button (about 10 mm).
9
The charging process is terminated and the charging
plug in the device is unlocked.
EN
23

Publicidad

Tabla de contenido
loading

Tabla de contenido