Resistance / Continuity Measurement (Mω Position); Connections; Pre-Measurement Settings; Instrument Settings - Chauvin Arnoux C.A 6470 Manual De Instrucciones

Controlador de tierra y de resistividad
Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

4.2 RESISTANCE / CONTINUITY MEASUREMENT (mΩ Ω Ω Ω position)
The instrument is designed to measure resistances of up to 100 kΩ; the measurement DC current is
≥200mA up to 20Ω (IEC standard 61557-4).
4.2.1

CONNECTIONS

2-pole connection
H
H
R
R
E
E
4.2.2

PRE-MEASUREMENT SETTINGS

4.2.2.1

INSTRUMENT SETTINGS

Before performing the measurement, use the
→ select the measurement mode (MANUAL or AUTOmatic),
→ select the number of poles for the measurement (2 or 4 poles),
→ in manual mode, select the measurement current polarity.
By its default configuration, the instrument places
itself in MANUAL mode and performs a 2-pole measurement.
4.2.2.2

MEASUREMENT CORD COMPENSATION :

For 2-pole measurement only, in manual or automatic mode.
The cord compensation function can also be used for coupling measurements before
performing the last 2-pole measurement (see §4.2.2.2).
→ → → →
Cord compensation is not possible during a measurement.
!
- short-circuit the measurement cords,
nd
- press the 2
key then the START/STOP pushbutton.
R
R
R
0
0
0
- the
symbol is displayed once the compensation is achieved: this function will be
used until the rotary switch position is changed.
Note : if the compensation resistance is > 5
R
R
R
0
0
0
symbol will disappear.
4.2.3
MEASUREMENT & RESULTS
At the start of the measurement,:
- the instrument measures U
measurement) : if greater than 60V
4-pole connection
H
H
S
S
R
R
ES
ES
E
E
CONFIG
CONFIG
CONFIG
and
keys to successively :
DISTANCE
DISTANCE
Ω Ω Ω Ω
, or in the event of an incorrect connection, the
(2-wire measurement) or U
H-E
, the measurement is refused,
peak
42
and U
(4-wire
S-ES
H-E

Publicidad

Tabla de contenido
loading

Tabla de contenido