Commissioning And Operation; Error And Warning Messages; Service And Repairs - Aventics AF2 Instrucciones De Servicio

Sensor de medición de caudal
Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 62
AVENTICS | AF2 | R412026496–BAL–001–AA | English
8/2
Qa Menu
This menu contains the settings for the analog output.
Assigning measurement parameters to the current output
O
Go to the Mode submenu to assign measurement parameters, such as flow, temperature, or
pressure, to the current output.
Assigning the full scale value (MBE)
O
Go to the High submenu and set the full scale value to 20 mA.
Assigning the measurement range start value
O
Go to the Low submenu and set the measurement range start value to 4 mA.
Setting the inversion of the current output
O
Go to the Polarity submenu to set if the current output should be inverted.
Setting the current output behavior in case of a device failure
O
Go to the Fail submenu to set if the behavior of the current output if a failure occurs.
Setting a predefined current value
O
Go to the Simulate submenu to set a predefined current value.
8

Commissioning and Operation

If no entry is made for longer than 2 minutes, the display will return to display mode.
Unconfirmed settings will not be taken over.
Before commissioning the system, the following steps must have been carried out and
completed:
W
You have fully mounted and connected the Durchflusssensor, in accordance with the
installation conditions (see also "5 Assembly").
W
You have carried out the required pre-settings and configuration.
Dangerous system operating states from incorrect settings on the flow rate sensor or if the
maximum/minimum flow rate sensor operating voltage is exceeded
Danger of injury and system damage from uncontrolled system operating states.
O
Do not make any improper changes to the Durchflusssensor during operation. Note that
the any settings become immediately effective when they are confirmed!
O
Exchange faulty flow rate sensors immediately!
O
Do not disconnect the Durchflusssensor from the voltage source during operation!
To commission the flow rate sensor:
1. Apply the operating voltage.
2. Pressurize the system component the Durchflusssensor is connected to.
3. The sensor performs a self-test and is then ready for use. The measured value menu is
displayed.
For problems during commissioning, see "11 Error and Warning Messages".
The Durchflusssensor does not have a main switch. Once you have connected the device
to the power pack and this has been connected to the mains, the Durchflusssensor is
turned on and ready for use. To turn it off, simply disconnect the power pack from the
power supply.
Short commissioning (with factory setting)
Short commissioning can be used for applications under reference conditions, see "Installation
Conditions".
Note for the IO-Link version:
If digital outputs Q1 and Q2 are used as IO-Link, frequency, or pulse output,
simultaneously with analog outputs Qa and Q2, the precision of the analog outputs may
be impaired.
9

Service and Repairs

The flow rate sensor is maintenance-free.
Only use water and, if necessary, a mild cleaning agent for cleaning.
Information on filter maintenance can be found in the filter instructions R412013436 (Filter AS1/
AS2/AS3/AS5).
10 Disassembly
System is under high pressure
Danger of injury and system damage from uncontrolled system operating states.
O
Make sure that the system component the Durchflusssensor is installed in is not under
pressure or voltage before beginning disassembly.
1. Make sure that the system is not under voltage or pressure.
2. Loosen and remove all connections.
3. Loosen the flow rate sensor from the pressure connection using an open end wrench (thread
connection) or pull the Durchflusssensor straight out of the push-in fitting.
WARNING
CAUTION

11 Error and Warning Messages

The following error and warning messages may appear in the flow rate sensor display if the
relevant error status results from a certain condition.
There are three classifications: info, warning, and error.
The table below lists all error messages with their corresponding error level.
Message
Classification
Memory Invalid
Error
No MQTT Connection
Warning
Simulation active
Info
Q1/2 Overtemp
Warning
Q1 Shortcut
Warning
Q2 Shortcut
Warning
Q2/a Overload
Warning
Q2/a OverTemp
Warning
Q2 PulseConfig
Warning
Qa Overload
Warning
Qa OverTemp
Warning
Flow low Info
Info
Flow high Info/Warning
Info/Warning
Pressure low
Warning
Pressure high
Warning
Temperature low
Warning
Temperature high
Info/Warning
Pressure low/high Error
Error
Temperature low/high Error
Error
Energy Counter off - Air only
Info
Voltage low for Q1/2
Info
Voltage low for Q2/a, Qa
Info
Voltage low for IO-Link
Info
Q1 Config out of Range
Info
Q2 Config out of Range
Info
Qa Config out of Range
Info
Invalid Medium + RefCond
Warning
Supply Voltage too low/high!
Warning
Internal Temperature too low/
high!
12 Disposal
Dispose of the packaging and used parts in accordance with the regulations of the country where
used.
19
Description
The sensor memory is damaged. The
flow rate sensor must be replaced.
No connection possible to MQTT
Broker.
Simulation active (output signal or
process variable)
Driver overload for switch output Q1/
Q2.
Short circuit at Q1
Short circuit at Q2
Q2/a: No current flow.
-Line not connected?
-Load resistance too high?
Q2/a: Excessive output driver
temperature
-Ideal: load of 500 ohms
-Ambient temperature too high?
Implausible configuration of Q2
pulse output
See Q2/a Overload
See Q2/a OverTemp
Info: MBE -5%
Info: Standard MBE +5%
Warning: Extended MBE +5%
Increase pressure
Reduce pressure
Increase temperature to the
specified value (see "13 Technical
Data").
Reduce temperature to the specified
value (see "13 Technical Data").
Process pressure outside
permissible pressure range
Temperature of the process medium
outside the permissible temperature
range
Medium = Air => Formula for energy
counter only stored for air, therefore
without function
Adjust voltage to the specified value
(see "13 Technical Data").
Adjust voltage to the specified value
(see "13 Technical Data").
Adjust voltage to the specified value
(see "13 Technical Data").
Switching points parameterized
outside the measurement range
Switching points parameterized
outside the measurement range
Switching points parameterized
outside the measurement range
RefCond only valid for air
Adjust voltage to the specified value
(see "13 Technical Data").
Adjust temperature to the specified
value (see "13 Technical Data").

Publicidad

Tabla de contenido
loading

Tabla de contenido