7. Installing the grille
Fig. 7-6
Fig. 7-8
Fig. 7-9
A
Fig. 7-10
7.3.2. Temporary installation of the grille (Fig. 7-6)
• Align the electric component box of the main unit and the receiver of the grille,
and then temporarily secure the grille using the bell shaped holes.
* Make sure that the lead wiring of the grille does not get pinched between the
7.3.3. Securing the grille (Fig. 7-7)
• Secure the grille to the main unit by tightening the previously installed 2 screws
(with captive washer) as well as the 2 remaining screws (with captive washer).
* Make sure that there are no gaps between the main unit and the grille or the
Fig. 7-7
7.3.4. Wire connection (Fig. 7-8)
• Be sure to connect the unit to the connector (white: 10-pole/red: 9-pole). Next,
attach the white glass tube that comes with the main unit so that the tube covers
the connector. Close the opening of the glass tube with the band.
• Make sure that there is no slack in the each lead wire at the fastener on the grille.
7.4. Locking the up/down airflow direction (Fig. 7-9)
The vanes of the unit can be set and locked in on up or down orientation depending
upon the environment of use.
• Set according to the preference of the customer.
The operation of the fixed up/down vanes and all automatic controls cannot
be performed using the remote controller. In addition, the actual position of the
vanes may differ from the position indicated on the wired remote controller.
Turn off the main power switch.
Injuries and or an electrical shock may occur while the fan of the unit is rotating.
Button
Disconnect the connector for the vane motor of the vent that you want to lock.
(While pressing the button, remove the connector in the direction indicated by
Vane motor
the arrow as shown in the diagram.) After removing the connector, insulate it
Up/down vanes
Connector
with tape.
To adjust the desired airflow direction, slowly move the up/down vanes within
the specified range. (Fig. 7-10)
Specified range
Up/down airflow
direction
• The vanes can be set between 21 and 30 mm (13/16 and 1-3/16 inch).
Measurement standard
position of grille
Caution:
Up/down vanes
Do not set the up/down vanes passed the specified range. Condensation
could form on and drop from the ceiling, or the unit could malfunction.
grille and the main unit.
Main unit
Electric component box
Screw with washer (for temporary use)
Screw with washer (Accessory)
Grille
Bell shaped hole
grille and the ceiling.
Ceiling
Main unit
Grille
Make sure that there are no gaps.
Fastener (Accessory)
White glass tube
Connector of the main unit
Connector of the grille
Band (Accessory)
Horizontal 30° Downward 45° Downward 55° Downward 70°
21 mm
25 mm
A
13/16 inch
31/32 inch
28 mm
30 mm
1-3/32 inch
1-3/16 inch
11