Electrical Work - Mitsubishi Electric Mr.SLIM SLZ-KA09NA Manual De Instalación

Ocultar thumbs Ver también para Mr.SLIM SLZ-KA09NA:
Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

5. Refrigerant pipe and drain pipe
Max. 65ft.
5 to 7 ft
Fig. 5-5
1-3/16 1-3/16 1-3/16
7/16
Fig. 5-6

6. Electrical work

CN105
RED
Electric component cover
Electric component box
Indoor/outdoor unit connecting terminal
Wired remote controller terminal
Fig. 6-1
Max. 6 in.
(inch)
,
Indoor controller board
Power board
Indoor - outdoor connecting cable of Location
Remote control cable of Location
5.4. Drainage piping work (Fig. 5-5)
• Use VP25 (O. D. ø32 mm, 1-1/4 inch PVC TUBE) for drain piping and provide
1/100 or more downward slope.
• Be sure to connect the piping joints using a polyvinyl type adhesive.
• Observe the figure for piping work.
• Use the included drain hose to change the extraction direction.
Correct piping
Wrong piping
Insulation (9 mm, 3/8 inch or more)
Downward slope (1/100 or more)
Grouped piping
O. D. ø32 mm, 1-1/4 inch PVC TUBE
Make it as large as possible
Indoor unit
Make the piping size large for grouped piping.
Downward slope (1/100 or more)
O. D. ø38 mm, 1-1/2 inch PVC TUBE for grouped piping.
(9 mm, 3/8 inch or more insulation)
Up to 500 mm, 19-11/16 inch
1. Connect the drain socket (supplied with the unit) to the drain port. (Fig. 5-6)
(Affix the tube using PVC adhesive then secure it with a band.)
2. Install a locally purchased drain pipe (PVC pipe, O.D. ø32 mm, 1-1/4 inch).
(Affix the pipe using PVC adhesive then secure it with a band.)
3. Insulate the tube and pipe. (PVC pipe, O.D. ø32 mm, 1-1/4 inch and socket)
4. Check that drain flows smoothly.
5. Insulate the drain port with insulating material, then secure the material with a
band. (Both insulating material and band are supplied with the unit.)
Main unit
Insulating material
Band (large)
Drain port (transparent)
Insertion margin
Matching
6.1. Indoor unit (Fig. 6-1)
1. Remove 2 screws to detach the electric component cover.
2. Route each cable through the wiring intake into the electric component box.
(Procure power supply cable and control cable locally.)
3. For radio frequency interface
Connect the electric cord of radio frequency interface securely to CN105 (RED)
on indoor controller board.
For wired remote controller
Securely connect the power supply cable and control cable to the terminal
blocks.
4. Secure the cables with clamps outside the electric component box.
5. Attach the electric component cover as it was.
Do not allow slackening of the terminal screws.
Always install earth.
(Earth cable dia: Thicker than 1.6 mm, 5/8 inch (AWG14))
Fix power supply cable and control cable to electric component box by using
buffer bushing for tensile force. (PG connection or the like.)
Tape is affixed over the conduit hole used for connecting the electric wiring.
Please remove this tape if making a connection through the hole.
Support metal
Air bleeder
Raised
Odor trap
Drain pipe (O.D. ø32 mm, 1-1/4 inch PVC TUBE)
Insulating material (purchased locally)
Transparent PVC pipe
O.D. ø32 mm, 1-1/4 inch PVC TUBE
(Slope 1/100 or more)
Band (small)
Drain socket
7

Publicidad

Capítulos

Tabla de contenido
loading

Este manual también es adecuado para:

Mr.slim slz-ka12naMr.slim slz-ka15na

Tabla de contenido