Bus Protocol; Sm 111 Sensor Detection - Grundfos IO 111 Manual De Instrucciones

Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 60

6.6 Bus protocol

By setting the bus protocol, the type of bus
connection is chosen.
GENIbus is a Grundfos standard protocol for
Grundfos products.
The Modbus protocol is used for communication
between the IO 111 and a control unit from another
supplier.
ON
Bus protocol
1 2 3 4 5 6 7 8 9 10
GENIbus
Modbus

6.7 SM 111 sensor detection

First time voltage is applied, the SM 111 will check all
inputs to detect which sensors are connected. If a
valid signal is measured, the SM 111 will register that
a sensor is present and save the status.
If the IO 111 indicates a sensor error or configuration
error, the sensor detection must be changed, see
12. Fault finding.
Sensor detection
Activated
Set back the DIP switch
14
DIP
Description
Grundfos standard protocol for communication between
Grundfos products
8
See www.grundfos.com, WebCAPS, Literature,
Accessories, Accessories, electrical and Operating the
IO 111 via Modbus, document number 96623373.
8
Change DIP switch No 9 on the IO 111 from OFF to
ON.
After approx. 5 seconds, the SM 111 will reset, and
the sensor detection is completed. Then set the DIP
switch to OFF again.
ON
DIP
1 2 3 4 5 6 7 8 9 10
9
9
Description
Change DIP switch No 9 on the IO 111
from OFF to ON. After approx.
5 seconds, the SM 111 will reset, and
the sensor detection is completed.
Set the DIP switch to OFF.

Publicidad

Tabla de contenido
loading

Tabla de contenido