Approval - Grundfos IO 111 Manual De Instrucciones

Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 60
The IO 111 operates with two categories of fault:
1. Alarm. The pump stops. The fault is a primary
functionality (e.g. too high motor temperature).
The relay opens and breaks the connection
between T1 and T2 (pos. 1) in case of alarm or if
the IO 111 is not connected to the power supply.
Alarm is indicated by the indicator lights on the
front of the IO 111 and via the three digital
outputs (pos. 16).
2. Warning. The pump does not stop. The fault is a
secondary functionality (e.g. too much water in
the oil).
Warning is indicated by the indicator lights on the
front of the IO 111. The warning status can be
read via the digital outputs D7 and D8 (pos. 16).
1
2
T1 T2
G1 A1 G2 A2 K1 K2 R1 R2
16
D1 D2 D3 D4 D5 D6 D7 D8
15
Reset
14
13
12
ON
DIP
11
1 2 3 4 5 6 7 8 9 10
P1 P2 P3 P4 P5
10
Fig. 1
IO 111 module
6
3
PE
4
A Y B
5
6
7
8
I1 I2 I3
9
Pos. Description
1
Terminal for alarm relay
Terminal for analog and digital inputs and
2
outputs
Terminal for supply voltage
3
(24 VAC/24 VDC)
Potentiometer for setting the warning limit of
4
stator insulation resistance
5
Terminal for RS485 for GENIbus or Modbus
Red indicator light. Alarm in case of too high
6
motor temperature.
Indicator lights for stator insulation
resistance.
7
Green = ok.
Yellow = warning.
Red = alarm.
Indicator lights for measurement of water in
8
oil
Terminal for measurement of stator
9
insulation resistance
10
Terminal for connection of pump sensors
11
DIP switch for configuration
Green indicator light. On when the pump is
12
running.
Red indicator light. Alarm in case of
13
moisture in the motor.
14
Button for reset of alarm
Yellow indicator light. Warning in case of
15
pump fault.
16
Terminal for digital outputs

2.1 Approval

The IO 111 is UL listed to US and
Canadian safety standards.