Parameter Management - Parker Hiross Hyperchill Manual De Uso

50hz
Ocultar thumbs Ver también para Hyperchill:
Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

4.4.1.2
Alarm relay management
0
Relay normally deactivated, excited by an alarm.
Relay normally excited (also with control OFF), deactivated
1
by an alarm.
Relay normally excited (only with control ON), deactivated
2
by an alarm or with control OFF.
4.4.2
Temperature control
PARAMETER
CODE
SEt
Temperature control set point
LI5
Set point lower limit
4.4.3
B1 sensor parameters
PARAMETER
CODE
cHAI
High temperature confi guration
HAI
High temperature alarm
LAI
Low temperature alarm
CAI
Sensor calibration
Low temperature alarm reset
dbI
diff erential
4.4.4
B2 sensor parameters
PARAMETER
CODE
cHA2
High temperature confi guration
HA2
High temperature alarm
LA2
Low temperature alarm
CA2
Sensor calibration
4.4.5
B3 sensors parameters
PARAMETER
CODE
HA3
High temperature alarm
LA3
Low temperature alarm
CA3
Sensor calibration
4.4.6
B3 sensors parameters
PARAMETER
CODE
HA3
High temperature alarm
LA3
Low temperature alarm
CA3
Sensor calibration
English
4.4.7
Compressor parameters
PARAMETER
Compressor 1 operation hour
counter
Compressor 2 operation hour
counter
Compressor 1 hour counter
threshold
TYPE
DEFAULT
Compressor 2 hour counter
20.0
D
threshold
5.0
U
4.4.8
Pump parameters
PARAMETER
TYPE DEFAULT
Pump stop delay
1
U
Pump start delay
60.0
D
4.4.9
Antifreeze heater parameters
-20.0
D
PARAMETER
0.0
U
Set point adjustment (B1)
1.0
U
Temperature control diff erential
(B1)
Antifreeze heater operating mode
TYPE DEFAULT
(see para. 4.4.8.1)
0
U
Antifreeze heater activation mode
60.0
(see para. 4.4.8.2)
U
3.0
Activation set point (B3)
U
4.4.9.1
FUA antifreeze heater operating mode
0.0
U
Heating element thermostatting by B1 with SEAsetting,
0
pump activation by B3 (ambient sensor) with ARA setting,
TYPE DEFAULT
heating element activated if pump is activated.
60.0
U
Heating element thermostatting + pump activation by B3
1
-20.0
U
(ambient sensor) with ARA setting.
0.0
U
Heating element thermostatting by B1 with SEAsetting,
2
pump activation by B3 (ambient sensor) with ARA setting,
heating element and pump with separate activation.
TYPE DEFAULT
4.4.9.2
AbrA antifreeze heater activation mode
60.0
U
-20.0
0
U
Activation only when controller is 'On'
0.0
1
U
Activation also when controller is 'Off '
Activation also when controller is 'Off ' . During heater op-
2
eration the pump is activated.
Hyperchill-Precision Control HLS076-116

4.5 Parameter management

4.5.1
CODE
TYPE
DEFAULT
1. 1. Turn the main swicth (QS) to "ON" and wait for the temperature
D
HI
-
visualization.
2. Press buttons "P3" and "P5" together, to enter into "dIrE" (D)
D
H2
-
parameters.
3. Press button "P4" to select "SEt" parameter, press the button
"P5" to confi rm.
tHI
0
U
4. Change the value, using the up and down arrow buttons "P3" and
"P4", then press button "P5" to confi rm.
tH2
0
U
6. Press the button "P3" to return on "dIrE" parameter.
7. Press the button "P5" to exit.
4.5.2
CODE
TYPE
DEFAULT
"B1" is the "set" sensor of the macchine.
dP5
5
1. Start the chiller.
U
2. Press the button "P4" to visualize the temperature of the next sen-
dPA
5
U
sor.
3. Press the button "P5" to visualize the sensors "b01" .."b02"....
It is recommended to leave on the display the B1 "set" sensor.
CODE
TYPE
DEFAULT
SEA
19.0
U
dIA
1.0
U
FUA
0
U
AbrA
2
U
ArA
5.0
U
Temperature setting (see fi g.1)
Visualization sensors B1,B2...
5/8

Publicidad

Tabla de contenido

Solución de problemas

loading

Este manual también es adecuado para:

Hls076Hls090Hls116

Tabla de contenido