Sime MURELLE HE ErP Serie Manual Del Usuario página 104

Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

of the curve.
ATTENTION:
- Observe the relevant standards and
regulations of the floor manufacturer!
- Proper functioning is ensured only
when the plant is correctly installed
(hydraulic system, electrical installa-
tion, settings)! If not observed, the
floor might get damaged!
4.6
FUNCTIONING ANOMALIES
When there is a functioning anomaly, an
alarm appears on the display and the blue
luminous bar becomes red.
Descriptions of the anomalies with relative
alarms and solutions are given below:
– LOW WATER PRESSURE ANOMALY
ALARM 02 (fig. 23/a)
If the pressure detected by the transdu-
cer is lower than 0.5 bar, the boiler
stops and the display shows the alarm
"ALL 02".
Bring the pressure back to normal by
acting on the loading knob. Lower the
knob and turn it anti-clockwise to open
until the pressure indicated by the
display is between 1 and 1.5 bars.
WHEN FILLING HAS BEEN COMPLETED,
CLOSE THE KNOB BY TURNING IT
CLOCKWISE.
If the load procedure has to be repea-
ted several times, it is advisable to
check that the seal of the heating cir-
cuit is intact (check that there are no
leaks).
104
[TVw]
55
50
45
40
35
30
25
20
0
1
5
7
1
X
A
1
TVw
Flow temperature setpoint
Tag
Period in days
x
Start day
A
Functional heating
B
Floor curing heating
5
10
15
B
A + B
OPEN
APRE
18
[Tag
]
25
Fig. 22/a
Fig. 23/a

Publicidad

Tabla de contenido
loading

Tabla de contenido