2.5.3
Maximum usable length
for separate ø 80 flues
The maximum overall length of ø 80 suc-
tion and exhaust flues is determined by
the load losses of the single accessories
installed and should not exceed 42 mm
H
O.
2
When the load loss exceeds 4 mm H
order to assure the correct operation of
the appliance, set the installer parameter
PAR 9 as indicated in TABLE 2 (see point
3.3 to access installer parameters) and
Type B
KEY
1
90° MF polypropylene curve (6 pcs.) code 8077450
2 a Polypropylene extension L. 1000 (6 pcs.) code 8077351
2 b Polypropylene extension L. 500 (6 pcs.) code. 8077350
3
Hinged tile code 8091300
4
Roof terminal kit L. 1381 code 8091204
5
Polypropylene extension L. 250 with socket code 6296513
6
45° MF polypropylene curve (6 pcs.) code 8077451
7
Exhaust terminal code 8089501
8
Internal-external ring nut kit code 8091500
11
Rubber gasket ø 80 (supplied as standard)
proceed with calibrating CO
mum and minimum capacity as specified
in point 4.2.2.
2.5.4
Maximum usable
length for coaxial ø 80/125 flues
O, in
In installations with ø 80/125 coaxial
2
exhaust, the maximum horizontal length
including the 90° curve, should not exceed
4 m when the boiler is supplied at the G20
and 3 m when it is supplied G31.
at the maxi-
In roof exhausts, it must not be greater
2
than 5 m straight vertical lines when the
boiler is supplied at G20 and 4 m when
supplied at G31.
WARNING: In order to assure the correct
operation of the appliance, set the instal-
ler parameter PAR 9 as indicated in
TABLES 3-3/a (see point 3.3 to access
the installer parameters) and proceed
with calibrating CO
minimum capacity as specified in point
4.2.2.
ø 80 ACCESSORY LOAD LOSS TABLE
Accessory ø 80
90° MF polypropylene curve
45° MF polypropylene curve
Polypropylene extension L. 1000
Polypropylene extension L. 500
Roof exit terminal L. 1381
Exhaust terminal
Polypropylene extension L. 250 with socket
WARNING !
When load loss of the individual accessories connected
exceeds 4 mm H
O, in order to assure the correct ope-
2
ration of the appliance, set the installer parameter PAR
9 as indicated in TABLE 1 (see point 3.3 to access the
installer parameters).
TABLE 1
Load loss
(mm H
O)
2
0 - 4
4 - 8
8 - 12
12 - 16
16 - 20
20 - 24
24 - 28
28 - 32
32 - 36
36 - 40
40 - 42
WARNING:
Before installing accessories, lubricate the
internal part of gaskets with silicon-based pro-
ducts. Avoid using oils and greases.
at the maximum and
2
Load loss
(mm H
O)
2
3,5
2,3
1,4
0,7
5,0
4,0
0,3
PAR 9
(long chimneys)
0
1
2
3
4
5
6
7
8
9
10
Fig. 6
ES
PT
ENG
77