TECHNICAL DATA
MODEL
TYPE
POWER
(1)
OUTPUT
(1)
FUEL
- net calorific value
- density
- viscosity at 20 °C
OPERATION
NOZZLES
STANDARD APPLICATIONS
AMBIENT TEMPERATURE
COMBUSTION AIR TEMPERATURE
ELECTRICAL SUPPLY
ELECTRIC MOTOR
MOTOR CAPACITOR
IGNITION TRANSFORMER
PUMP
output (at 12 bar)
pressure range
fuel temperature
ELECTRICAL POWER CONSUMPTION
PROTECTION LEVEL
NOISE LEVEL
SOUND PRESSURE
(2)
SOUND POWER
Reference conditions: Ambient temperature 20°C - Barometric pressure 1013 mbar - Altitude 0 m a.s.l.
(1)
Sound pressure measured in manufacturer's combustion laboratory, with burner operating on test boiler and at maximum rated output. The
(2)
sound power is measured with the "Free Field" method, as per EN 15036, and according to an "Accuracy: Category 3" measuring accuracy,
as set out in EN ISO 3746.
VARIANTS
Model
RL 34/1 MZ
ACCESSORIES
:
(optional)
• KIT LONG HEAD
• KIT CLEAN CONTACTS
• KIT POST-PURGING
• KIT HOURCOUNTER
• KIT GROUND FAULT INTERRUPTER
• RADIO DISTURBANCEPROTECTION KIT
If the burner is installed in places particularly subject to radio disturbance (emission of signals exceeding 10 V/m)
owing to the presence of an INVERTER, or in applications where the length of the thermostat connections exceeds
20 metres, a protection kit is available as an interface between the control box and the burner.
•
DEGASSING UNIT
It may occur that a certain amount of air is contained in the light oil sucked up by the pump. This air may originate from the light oil itself as a con-
sequence of depressurisation or air leaking past imperfect seals.
In double-pipe systems, the air returns to the tank from the return pipe; in single-pipe systems, the air remains in circulation causing pressure var-
iations in the pump and burner malfunctions.
For this reason, we advise installing a degassing unit near the burner in single-pipe installations. Degassing units are provided in two versions:
CODE 3010054 without filter
CODE 3010055 with filter
Degassing unit characteristics
• Burner output
• Light oil pressure
• Ambient temperature
• Light oil temperature
• Attachment connectors
kW
Mcal/h
kg/h
kWh/kg
Mcal/kg
kg/dm
2
mm
number
°C max
Hz
rpm
F/V
V1 - V2
I1 - I2
kg/h
bar
°C max
W max
dB(A)
Electrical
Code
supply
3470110
single-phase
3470111
single-phase
: 80 kg/h max
: 0.7 bar max
: 40 °C max
: 40 °C max
: 1/4 inch
RL 34/1 MZ
971 T
107 - 398
92 - 342
9 - 33.6
LIGHT OIL
11.8
10.2 (10,200 kcal/kg)
0,82 - 0,85
3
/s max 6 (1.5 °E - 6 cSt)
• Intermittent (min. 1 stop in 24 hours)
• Single-stage (all - nothing)
2
Boilers: water, steam, diathermic oil
°C
0 - 40
60
V
230 ~ +/-10%
50/60 - single-phase
2800
W
300
V
220 - 240
A
2.4
12.5/450
230 V - 2 x 12 kV
0.2 A - 30 mA
45
7 - 14
60
600
IP40
68
79
Blast tube
length mm
216
351
2
Code 3010426
Code 3010419
Code 3010453
Code 3010450
Code 3010448
Code 3010386