7.4

Before switching on

7.5

Switching on and off

7.6

During operation

Installation and operating instructions Wilo-Rexa CUT GI
Commissioning
▪ For star-delta activation motors swap the connections of two windings (e.g. U1/V1 and U2/
V2).
Before switching on check the following points:
▪ Check that the installation has been performed correctly and according to the locally appli-
cable regulations:
– Pump connected to electrical ground?
– Has the routing of the power supply cable been checked?
– Has the electrical connection been carried out in line with the regulations?
– Are mechanical components correctly attached?
▪ Check the level control device:
– Can float switches move freely?
– Have switching levels been checked (pump on, pump off, minimum water level)?
– Has additional dry-running protection been installed?
▪ Check operating conditions:
– Has the min./max. temperature of the fluid been checked?
– Has the maximum immersion depth been checked?
– Has the operating mode depending on the minimum water level been defined?
– Is the maximum switching frequency being adhered to?
▪ Check installation site/operating space:
– Is the pipe system on the pressure side free of deposits?
– Has the inlet or pump sump been cleaned and is free of deposits?
– Are all gate valves open?
– Has the minimum water level been defined and monitored?
The hydraulics housing must be completely filled with fluid and there must be no air cush-
ions in the hydraulics. NOTICE! If there is a danger of air cushions in the system, provide
suitable venting devices!
During the start-up procedure, the rated current is temporarily exceeded. During operation,
the rated current must not be exceeded again. CAUTION! If the pump does not start, im-
mediately switch off the pump. First repair the fault before re-activating the pump!
Position pumps in portable installation on a firm foundation. Before switching on pumps
which have fallen over, make sure to re-position them. In the case of problematic surfaces,
tightly screw the pump.
Pumps with bare cable end
The pump must be switched on and off via a separate operating point (on/off switch,
switchgear) provided by the customer.
WARNING
Amputation of limbs due to rotating components!
People must be kept out of the pump's working area! There is a risk of (serious) injury due
to rotating parts! During activation and operation no persons should be allowed in the
working area.
WARNING
Danger of burning due to hot surfaces!
The motor housing can get hot during operation. It can lead to burns. Allow the pump to
cool down to ambient temperature after switching off!