Fan Replacement
Under normal conditions, the original fan installation will last several years. The fan assemblies are replaceable. Replacements can be found
at tripplite.com/support.
CAUTION: The fan circuitry is not isolated from AC mains. Turn off power to the UPS prior to fan replacement. Fan
replacement must be performed only by qualified electrical service personnel.
Before removing the fan assemblies, note the fan orientation. For proper installation and connectivity, the fans must
remain in their original orientation.
1
Remove the six front screws from the front bezel, then remove
the bezel from the UPS. Hang the bezel on the available hook.
1
Disconnect the fan cable(s), located to the left of the fans.
3
3
2
To replace the left-side fan or right-side fan, use a flat head
screwdriver to remove the top-left screw and the bottom-right
screw attached to each fan.
2
Install the replacement fan(s). Connect the cable(s) in the same
4
order as in step 3 and secure the fan(s) to the UPS in the same
location and orientation as in step
Reattach the front bezel to the UPS and secure with the screws
5
removed in step
1
.
5
32