8022692.10DR | SICK
Subject to change without notice
1...3 sec.
Figure 11: WTS16 sensing range setting
2
Turn the potentiometer a fraction counterclockwise until the yellow LED indicator
no longer lights up. The sensing range is now located a fraction above the con‐
veyor belt.
Figure 12: WTS16 sensing range setting
3
The conveyor belt should now be put into operation without any objects. If the yel‐
low LED indicator does not light up during the test run, the sensing range is set
correctly.
Figure 13: WTS16 sensing range setting
4
If the object is in the path of the beam and the yellow LED indicator lights up, the
sensing range is set correctly.
6
COMMISSIONING
13