Sime MURELLE HE 70 R ErP Instrucciones Originales página 79

Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

BOILER 
.
Instant.with.deviator.valve..
.
and.flowmeter
.
.
Instant.with.deviator.valve,..
.flowmeter.and.solar.combination
.
D.H.W..tank.with.
.deviator.valve.and.boiler.sensor..
.
vers..T.(LOW.INERTIA).
.
On.board.D.H.W..tank.with
.deviator.valve.and.D.H.W..sensor...
.
(LOW.INERTIA).
. R emote.D.H.W..tank.with.deviator.
. valve.and.D.H.W..thermostat...
.
or.heating.only.vers..T/R.boiler
.
(LOW.INERTIA)
.
On.board.D.H.W..tank.with
.double.pump.and.D.H.W..sensor...
.
vers..T/R.boiler.
.
(LOW.INERTIA)
.
On.board.D.H.W..tank.with
.
double.pump.and.D.H.W..
. thermostat.vers..T/R.boiler...
.
(LOW.INERTIA).
.
Heating.only.with
.
antifreeze.sensor...
.
(LOW.INERTIA)
NOTE:  the  inside  of  the  upper  door  of 
the  boiler  panel  has  a  label  with  the 
values that have to be set for PAR 1 and 
PAR 2 (fig. 19). 
5
3.3.2 
Warning
Should. the. boiler. operation. not. be. opti-
mal. but. no. alarm. sets. off,. press. the.
3
button..
.until.info.70.and.the.warning.
code.associated.to.the.ongoing.event.are.
1
displayed.. Once. optimal. operation. is.
restored,.info.70.will.display:."-.-".
Below.is.the.table.of.warning.codes:.
2
 CODE 
DESCRIPTION
4
. E0.
Reduced.capacity.operation.
.
.
(∆t.between.delivery.and.return.
.
.
over.40°C)
. E1.
Shorted.external.sensor.(SE)
  E2.
Preheating.function.active
. E3.
TBD
. E4.
TBD
. E5.
TBD
. E6.
TBD
. E7.
TBD
. E8.
TBD
. E9.
TBD
PAR 2
1
EXPANSION CARD
2
PAR.DESCRIPTION...
.
.
40.
Number.of.expansion.boards..
3
41.
Mix.valve.stroke.time.
42.
Priority.of.D.H.W..over.mixed.zone.
.
.
43.
Floor.drying.
4
.
.
.
.
.
.
5
44.
Type.of.solar.system.
45.
t.solar.collector.pump.1.
46.
Solar.integration.delay..
47.
Tmin.solar.collector.
48.
Tmax.solar.collector.
6
PARAMETERS RESTORATION 
PAR.DESCRIPTION...
8
.
.
49.*. Reset.default.parameters.
.
(par.01.-.par.02.=.."-")
9
*   In case of difficulty in understanding the current setting or in case of an anomalous or 
  incomprehensible conduct of the boiler, we suggest to restore the initial values of the parameters 
  setting PAR 49 = 1 and the  PAR 1 and PAR 2 as specified at point 3.3.1.  
When the appliance is installed in sequence/cascade (modular system 
with  several  generators)  it  is  necessary  to  set  the  following  INST 
parameter on all connected burners:
PAR 15  =  
Set the following INST parameter if polypropylene smoke collectors 
with a clapet valve are used in sequence/cascade installations:
PAR 1    =  
5
In addition, when the number of boilers in cascade is more than two, 
configure the parameters OEM A1 of the MASTER boiler.
To access the OEM parameters press simultaneously the buttons (
and 
) for 2 seconds. Entered in the INST level again press simulta-
neously he buttons (
1
At  this  point  insert  the  access  code  formed  by  this  sequence  of 
INSTALLATOR BUTTONS: 
" + / - / < / > / < ".  
2
Set the parameter:
PAR A1   =   
PARAMETERS INSTALLER
RANGE.
.
0.....3.
0.....199.
0.=.Paralle.
1.=.Absolute
0.=.No.activated.
1.=.Curve.A
2.=.Curve.B
3.=.Curve.A+B
1.....8.
PAR.74.OEM.-.1....50.
"--",.0.....199.
"--",.-30.....0.
"--",.80.....199.
RANGE.
.
--.,.1.
CASCADE CONNECTION PARAMETERS
0 for the first boiler (MASTER)
1 .... 7 for the other boilers (SLAVE)
(Avoid assigning the same number to SLAVE boilers)
61 (for NATURAL GAS boilers)
63 (for PROPANE boilers)
5
5
3
3
3
 and 
) for another 2 seconds. 
1
1
2
2
4
Number of cascade generators (3 ... 8)
4
4
UNIT.OF.
INC/DEC..
DEFAULT
MEASUREMENT.
UNIT.
SETTING
=.
1.
0
10.sec..
1.
12
=.
=.
1
=.
=.
0
=.
1.
1
°C.
1.
8
Min..
1.
0
°C.
1.
-.10
°C.
1.
120
UNIT.OF.
INC/DEC..
DEFAULT
MEASUREMENT.
UNIT.
SETTING
=.
=.
=
5
1
2
ES
PT
ENG
3
4
79