29..The.boiler.functional.excluding.the.
function.ZONE.MIX/SOLAR..
–. HEATING RETURN SENSOR ANOMALY 
"ALL 30" (fig. 23/24)
. When. the. heating. return. sensor. (SR).
is.open.or.shorted,.ALL.30.shall.be.di-
splayed.
. During. such. anomaly,. the. boiler. will.
continue.to.operate.normally.
Apre
–. CASCADE  DELIVERY  SENSOR  ANO-
MALY "ALL 31" (fig. 23/25)
. When. the. cascade. delivery. sensor.
(SMC).is.open.or.shorted,.ALL.31.shall.
be.displayed..
. During. such. anomaly,. the. boiler. will.
continue.to.operate.normally.
2
–. THREE-ZONE  SYSTEM  CONFIGURA-
TION ANOMALY "ALL 32" (fig. 23/26)
. When.the.boards.connected.to.the.RS-
485.are.not.enough.and/or.at.least.one.
of.them.it.is.not.mixing.zone.board,.the.
boiler.stops.and.anomaly.ALL.32.is.di-
splayed..
Apre
. The. boiler. restarts. when. the. boiler.
three-zone.system.configuration.is.ac-
tivated
2
–. RS-485  BOARD  COMMUNICATION 
ANOMALY IN MODBUS MODE "ALL 33" 
2
(fig. 23/27)
. When.PAR.16.is.different.from."-.-"and.
Circuito
riscaldamento 2
there. is. no. communication. between.
the. boiler. board. and. the. RS-485. bo-
ard.in.MODBUS.mode.for.at.least.four.
minutes,.the.boiler.stops.and.anomaly.
Circuito
riscaldamento 3
(impianto tre
zone)
2
ALL.33.is.displayed..
. The.boiler.restarts.when.communica-
tion.is.restored.or.when.PAR.16.=."-.-".
is.set.
–. RS-485  BOARD  COMMUNICATION 
ANOMALY  IN  CASCADE  MODE  "ALL 
34" (fig. 23/28)
. When. PAR. 15. is. different. from. "-. -".
and.there.is.no.communication.betwe-
en.the.boiler.board.and.the.RS-485.bo-
ard.in.CASCADE.mode,.the.boiler.stops.
and.anomaly.ALL.34.is.displayed..The.
boiler.restarts.when.communication.is.
restored.or.when.PAR.15.=."-.-".is.set.
Fig..23/24
–. RS-485  AND  RS-485  COMMUNICA-
TION ANOMALY "ALL 35" (fig. 23/29)
.
When. PAR. 15. is. different. from. "-. -".
and.there.is.no.communication.betwe-
Circuito
riscaldamento 2
en. the. two. RS-485. boards,. the. boiler.
stops.and.anomaly.ALL.35.is.displayed..
The.boiler.restarts.when.communica-
tion.is.restored.or.when.PAR.15.=."-.-".
Circuito
is.set.
riscaldamento 3
Fig..23/25
(impianto tre
zone)
CAUTION:  In  the  event  of  sequence/ca-
scade connection, error codes 70 and 71 
will  appear  on  the  SIME HOME  remote 
control display:
-   ALARM 70
  When  an  anomaly  affects  cascade 
operation  (cascade  delivery  sensor 
Circuito
riscaldamento 2
ALL  31),  SIME HOME  remote  control 
Fig..23/26
display will show alarm 70. Verify the 
anomaly in the cascade.
-   ALARM 71
Circuito
riscaldamento 3
  When an anomaly occurs in one of the 
(impianto tre
zone)
2
modules  and  the  others  keep  ope-
rating  to  the  extent  permitted,  the 
SIME HOME  remote  control  display 
will  show  alarm  71.  Verify  the  ano-
maly in the cascade.
Fig..23/27
Fig..23/28
Fig..23/29
ES
PT
ENG
89