LIFE Plus Controller 4-8-12-16
Setting the Program(s) on Sensor Active.
• Press the
button to access the Controller's Settings.
• Press the
or
buttons to select SENS @ PRG
• Press the
or
button to select all 4 Programs (A, B, C, D) or ONLY one of
them:
Program A, or
Program B, or
Program C, or
Program D, or
ALL.
Note: SENS @ PRG page is available only if SENSOR is not set to OFF.
Setting Local Action on Sensor Active.
• Press the
button to access the Controller's Settings.
• Press the
or
buttons to select SENS-ACTN
• Press the
or
button to select one of the following Actions:
NONE ➞ No action
START ➞ Start the Program(s) selected in the SENS @ PRG page
STOP ➞ Stop the Program(s) selected in the SENS @ PRG page
SKIP ➞ Skip to the next programmed station for the Program(s) selected in the
SENS @ PRG page
HOLD ➞ Put on HOLD the Program(s) selected in the SENS @ PRG page
RAIN ➞ Put on RAIN the Program(s) selected in the SENS @ PRG page.
Note: SENS @ PRG page is available only if SENSOR is not set to OFF.
Setting the Meter Overflow Function.
Meter Overflow status is Normal if during Overflow calculation the number of pulses
per minute from the Water Meter is below the set Pulses/minute Threshold.
22
Meter Overflow status is Active if during Overflow calculation the number of pulses
per minute from the Water Meter is above the set Pulses/minute Threshold.
Setting Overflow Threshold.
• Press the
button to access the Controller's Settings.
• Press the
or
buttons to select OVER P/m.
• Press the
or
button to disable the Overflow function or to select the
Overflow threshold:
Off ➞ 001 . . ➞ . . 200 P/m (pulses per minute).
Note: selecting OFF the following 3 settings are not visualized.
Meter Overflow Delay to Overflow Active.
• Press the
button to access the Controller's Settings.
• Press the
or
buttons to select OVER-DELAY.
• Press the
or
button to disable Overflow delay or to set a delay time:
Off ➞ 1s . . ➞ . . 8m, increment in seconds.
Note: OVER-DELAY page is available only if OVER P/m is not set to OFF.
Setting the Program(s) on Overflow Active.
• Press the
button to access the Controller's Settings.
• Press the
or
buttons to select OVER @ PRG.
• Press the
or
button to select ALL 4 Programs (A, B, C, D) or ONLY one of
them:
Program A, or
Program B, or
Program C, or
Program D, or