Adress
30047
Holding registers (F3, F6, F16)
Address
40001-40010
40011
26
Mirka® Motor Drive Cabinet
Data type
Name
Uint16
Alarm status flag
Data type
Name
Char[20]
Device name
Uint16
Speed set-point
Description
Alarm status flag can at any given
time hold a
combination of values from the
list below. Check
the individual bits to determine
the type of alarms
that are currently triggered. This
flag is automatically
cleared after 5 seconds if the cause
of the alarm
trigger is no longer present.
0x0000 = Not triggered
0x0001 = Tool overheated
0x0002 = Motor drive overheated
0x0004 = Over-current
0x0008 = Under-voltage
0x0010 = Over-voltage
0x0020 = Self-test running
0x0040 = RPM drop
0x0080 = High current
0x0100 = Tool change in progress
0x0200 = Possible tool wiring fault
0x0400 = Factory reset mode
0x0800 = Write protection dis-
abled
Description
Max length 19 printable charac-
ters, e.g. "AIMD 749474379001".
Speed set-point, not the actual
speed, between 4,000–10,000
RPM.