TROUBLESHOOTING
Troubleshooting
Problem
Electrical Power Source Failure
Blow off Main
Switch Fuse
Blow off
No Activation of
Control
Unit Operation
Circuit Fuse
Indicator
Faulty Transformer of Indoor Unit
Disconnected Cable of Remote Control Panel to the Indoor Unit
Abnormality of Remote Control Switch
Incorrect
activation of
PCB
Faulty Indoor Fan Motor
Faulty Outdoor Fan Motor
Faulty magnetic switch for Outdoor Fan Motor
No Activation of
Faulty Compressor Motor of Compressor
Compressor and
Faulty Magnetic Switch for Compressor Motor
Fan Motor (In the
Case of Indicator
Incorrect activation of PCB
Activation of
Remote Control
Switch)
In case of 3~ unit installed
for first time, if an "05" code
is indicated on remote
control switch
Faulty Internal Thermostat for Indoor Fan Motor
Disconnected Wires between Indoor Unit and Outdoor Unit
Flickering of
Indicator and Lamp
Incorrect Activation of PCB
of "RUN" Switch
Tripped Float Switch for Drain (only in RCI Units)
Abnormality of Thermistor
No Speed Change
for Air Inlet Discharge Temp.
of Fan In spite of
Faulty Remote Control Switch
Adjustment
Faulty PCB of Indoor Unit
Abnormality of Thermistor
No Stopping
for Air Inlet Temperature
and Starting of
Compressor In
Faulty "TEMP" Switch of Remote Control Switch
spite of Adjusting
Faulty PCB of Indoor Unit
Thermostat
Faulty Cable of Remote Control Switch
All manuals and user guides at all-guides.com
Causes
Electrical Short Circuit to Earth
Faulty Compressor Motor
Faulty Indoor Fan Motor
Electrical Short Circuit between Different Phase
Wires
Electrical Short Circuit to Earth
Faulty Magnetic Switch for Compressor Motor
Disconnected Wire(s) to PCB of Indoor Unit
Faulty PCB of Indoor Unit
Disconnected Wire(s) to PCB
Faulty PCB of Indoor Unit
Phase protection Relay
Disconnected Wire(s) to the PCB
Faulty PCB of Indoor Unit
Faulty Thermistor
Disconnected Wire of Thermistor
Faulty Thermistor
Disconnected Wire of Thermistor
Solution
Wait for Recovering of Electrical Power Supply
Replace the Main Switch Fuse after Eliminating
Earthing
Replace the Compressor and the main Switch Fuse
Replace the indoor Fan Motor and the Main Switch
Fuse
Replace the Fuse
Replace the Fuse
Replace the magnetic Switch and the Fuse
Replace the Transformer
Replace the Cable
Check the connection of the Remote Control Cable.
Replace the Remote Control Switch.
Connect Wire(s) to the PCB
Replace the PCB of Indoor Unit
Replace the Indoor Fan Motor
Replace the Outdoor Fan Motor
Replace the magnetic switch of the Outdoor Unit
Replace the Compressor
Replace the magnetic switch
Connect Wire(s) to the PCB
Replace the PCB for Indoor Unit
Switch off the power supply of the unit, reverse 2 of
the phases, reapply the power and restart the unit
Replace the Indoor Fan Motor
Connect the Wires Correctly
Connect Wire(s) to the PCB
Replace the PCB for Indoor Unit
Adjust level of the Drain pan Repair or Replace the
Drain Discharge Mechanism. Remove the Clogged
Material
Replace the Thermistor
Connect the Wire to the Thermistor
Replace the Remote Control Switch
Replace the PCB of the Indoor Unit
Replace the Thermistor
Connect the Wire of Thermistor
Replace "TEMP" Switch of Remote Control Switch
Replace PCB of the Indoor Unit
Replace the Cable
PMGB0126A rev.2 - 11/2006