Hitachi HNE Serie Manual De Instalación Y Funcionamiento página 31

Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 49
REFRIGERANT PIPING &
REFRIGERANT CHARGE
11.4.2. REFRIGERANT PIPING SELECTION
Select the piping connection sizes according to the following
procedures:
Between Outdoor Unit and branch pipe:
-
Select the same pipe connection size as the pipe size of the
Outdoor Unit
Between branch pipe and Indoor Unit:
-
Select the same pipe connection size as the pipe size of the
Indoor Unit
Gas piping
Liquid piping
Unit
size
size
RASC-5
15.88 (5/8")
9.53 (3/8")
RASC-10
25.4 (1")
12.7 (1/2")
For RASC-10 units, use a reducer pipe in the following
installations:
Pipe
Installation
Distributor
Dimensions
type
Type
a
Gas
Ø 25.4 Ø 22.2
Single
-
Liquid Ø 12.7 Ø 9.53
Twin
TE-56N
Liquid Ø 9.53 Ø 6.35 indoor 2.0HP
Triple
TRE-810N
Liquid Ø 12.7 Ø 9.53
Quad
QE-810N
Liquid Ø 12.7 Ø 9.53
11.4.3. Twin, TRIPLE AND QUAD System Installation
Height Difference Between Indoor Units and Distributor
Install all indoor units at the same height. When the
height difference between the indoor units due to building
construction is necessary, this should be less than 0,5
meters. Install the branch pipe at the same height of indoor
units or lower, but never higher.
Sample: Twin system
Height difference between two
indoors. Smaller than 0.5m
Indoor units
Smaller than
0.5mm
Installing Distributor
1. Install the Distributor supplied by HITACHI on request
A tee can not be installed instead of a branch pipe.
Sample: Twin System
All manuals and user guides at all-guides.com
Distributor
Twin
Triple
Quad
TE-56N
-
-
TE-10N
TRE-810N QE-810N
a
Remarks
b
(*)
b
(*)
(*) Single installations with
-
RPI-10HP manufactured
from Feb'07, the reducer is
-
not required.
Branch pipe
2. Installing the Distributor.
Fix the branch pipe horizontally to the pillar, wall or ceiling.
Piping must not be fixed rigidly to the wall as thermal
expansion and contraction can cause pipe fracture.
Sample: Twin System
Horizontal
To indoor
unit
Fixing the branch pipie
To outdoor unit
to the surface of pillar
or wall
NOTE:
-
Fix the piping from outside of insulation or inserting
absorber between the pipe and a fixing metal.
3. Correct position of twin distributor
This is the correct position of twin Branch Pipe:
Up
Greater
than 0.5m
Main Pipe
Refrigerant direction
Down
This is wrong position.
Up
Main Pipe
Branch
Branch
pipe
pipe
Down
4. Correct position of Triple and Quad Distributor.
Install the header horizontally
Sample: Triple Branch pipe
Gas piping
Liquid piping
PMGB0126A rev.2 - 11/2006
To indoor
unit
Horizontal
Fixing the branch pipe
to ceiling or beam
Branch
Refrigerant
pipe
direction
Main Pipe
Main Pipe
Refrigerant
direction
Branch
pipe
19
Horizontal

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

Fsne serieFsn1e serie

Tabla de contenido