SAFETY SUMMARY
16. SAFETY SUMMARY & CONTROL DEVICE SETTING

16.1. INDOOR UNITS

Model
For the evaporator fan motor:
Internal thermostat
Cut-Out
Cut-In
For the control circuit:
Fuse capacity
Freeze protection thermostat:
Cut-out
Cut-in
Thermostat differential
16.2. OUTDOOR UNIT HEAT PUMP
Model
High Pressure Switch for
compressor
Pressure Switch for bypass
Crankcase heater
CCP Timer (1)
Fuse
Current Sensor (2)
Circuit Bracker
(1) CPU Control from Indoor Unit Non-Adjustable.
(2) CPU Cut-Out Control Value.
All manuals and user guides at all-guides.com
RCI
RCD
RPC
°C
145±5
130±5
135±5
°C
90±15
83±15
90±15
A
°C
°C
°C
RASC-5HNE RASC-10HNE
Cut-Out
MPa
4.15
Cut-In
MPa
3.20
Cut-Out
MPa
2.85
Cut-In
MPa
3.60
Output
W
Setting Time
min
Nominal current
A
Nominal current
A
Nominal current
A
RPI
RPK
RPF
140±5
130±5
130±5
90±15
83±15
83±15
5
0
14
2
–0.05
–0.05
4.15
–0.15
–0.15
+0.15
+0.15
3.20
–0.15
–0.15
+0.1
+0.1
2.85
–0.1
–0.1
0
0
3.60
–0.15
–0.15
40
90
3
2
20x2
32x2
17
17
8
8
PMGB0126A rev.2 - 11/2006
RPFI
Remarks
Automatic reset, non-
adjustable (each one
130±5
for each motor)
83±15
32