TROUBLESHOOTING
Problem
Tripped High Pressure
No Restarting of
Switch
Outdoor Fan Motor
and Compressor
after Stoppage
for Cooling
Operation (Lamp
of "RUN" Switch
and Indicator is
Flickered)
Tripped Overcurrent
relay for Compressor
Motor
Excessive Cooling Load
Insufficient Cooling
Too Low Pressure
(Lamp of "RUN"
Switch activates)
Excessively High
Pressure
Insufficient Heating
Too Low Pressure
(Lamp of "RUN"
Switch Activates)
(Only for Heat-
Pump Models)
Excessively High
Pressure
All manuals and user guides at all-guides.com
Causes
Obstacle to Air Intake of Air Discharge
for Outdoor Unit
Insufficient Air Intake or Air Discharge
Space for Outdoor Unit
Short Circuited Air Discharge for
Outdoor Unit
Faulty Outdoor Fan Motor
Overcharged Refrigerant
Clogged Capillary Tube
Excessively High Ambient
Temperature
Temperature of High Air Inlet
Temperature for Indoor Unit
Excessively High Discharge or Suction
Pressure
High or Low Voltage
Faulty Compressor Motor (After
Checked Electrical Resistance)
Faulty Overcurrent Relay
Faulty Starting Relay
Frequent start/stop compressor
Insufficiently Charged Refrigerant Gas
Refrigerant Gas Leakage
Clogged Strainer
Clogged Suction Piping
Clogged Air Filter
Obstacle to Air Intake or Air Discharge
for Indoor Unit
Faulty Indoor Fan Motor
Short Circuited Air Discharge for
Indoor Unit
Same as Tripped Air Discharge for
Indoor Unit
Clogged Strainer
Clogged Suction Piping
Obstacle to Air Intake or Air Discharge
for Outdoor Unit
Faulty Outdoor Fan Motor
Short Circuited Air Discharge for
Outdoor Unit
Faulty Thermistor(s) for Deicer
Same as Tripped Air Discharge for
Indoor Unit
Solution
Remove the obstacle
Keep the minimum Air Intake and Air Discharge Space
Remove Any Obstacle
Replace the Outdoor Fan Motor
Charge Correct Refrigerant Gas
Replace the Capillary Tube
See Unit Working Range
Reduce the Cooling Load
Same as Tripped High Pressure Switch Remedy Action
Obtain Correct Voltage
Replace the Compressor
Replace the Overcurrent Relay
Replace the Starting Relay
Replace the compressor
Reduce the Cooling Load
Charge Correct Refrigerant Gas
Repair Leakage and Charge Correct Refrigerant Gas
Repair or Replace the Strainer
Remove the Obstacle
Cleaning the Air Filter
Take Away the Obstacle
Replace the Indoor Fan Motor
Take Away any Obstacle
Same as Tripped High Pressure Switch Remedy Action
Repair or Replace the Strainer
Remove the Obstacle
Take away the obstacle
Replace the Outdoor Fan Motor
Take Away any Obstacle
Replace the Thermistor(s)
Same as Tripped High Pressure Switch Remedy Action
PMGB0126A rev.2 - 11/2006