TROUBLESHOOTING
Problem
•
Tripped High Pressure
No Restarting of
Switch
Outdoor Fan Motor
and Compressor
after Stoppage
for Cooling
Operation (Lamp
of "RUN" Switch
and Indicator is
Flickered)
•
Tripped Overcurrent
relay for Compressor
Motor
•
Excessive Cooling Load
Insufficient Cooling
•
Too Low Pressure
(Lamp of "RUN"
Switch activates)
•
Excessively High
Pressure
Insufficient Heating
•
Too Low Pressure
(Lamp of "RUN"
Switch Activates)
(Only for Heat-
Pump Models)
•
Excessively High
Pressure
All manuals and user guides at all-guides.com
Causes
•
Obstacle to Air Intake of Air Discharge
for Outdoor Unit
•
Insufficient Air Intake or Air Discharge
Space for Outdoor Unit
•
Short Circuited Air Discharge for
Outdoor Unit
•
Faulty Outdoor Fan Motor
•
Overcharged Refrigerant
•
Clogged Capillary Tube
•
Excessively High Ambient
Temperature
•
Temperature of High Air Inlet
•
Temperature for Indoor Unit
•
Excessively High Discharge or Suction
Pressure
•
High or Low Voltage
•
Faulty Compressor Motor (After
Checked Electrical Resistance)
•
Faulty Overcurrent Relay
•
Faulty Starting Relay
•
Frequent start/stop compressor
•
Insufficiently Charged Refrigerant Gas
•
Refrigerant Gas Leakage
•
Clogged Strainer
•
Clogged Suction Piping
•
Clogged Air Filter
•
Obstacle to Air Intake or Air Discharge
for Indoor Unit
•
Faulty Indoor Fan Motor
•
Short Circuited Air Discharge for
Indoor Unit
•
Same as Tripped Air Discharge for
Indoor Unit
•
Clogged Strainer
•
Clogged Suction Piping
•
Obstacle to Air Intake or Air Discharge
for Outdoor Unit
•
Faulty Outdoor Fan Motor
•
Short Circuited Air Discharge for
Outdoor Unit
•
Faulty Thermistor(s) for Deicer
•
Same as Tripped Air Discharge for
Indoor Unit
Solution
•
Remove the obstacle
•
Keep the minimum Air Intake and Air Discharge Space
•
Remove Any Obstacle
•
Replace the Outdoor Fan Motor
•
Charge Correct Refrigerant Gas
•
Replace the Capillary Tube
•
See Unit Working Range
•
Reduce the Cooling Load
•
Same as Tripped High Pressure Switch Remedy Action
•
Obtain Correct Voltage
•
Replace the Compressor
•
Replace the Overcurrent Relay
•
Replace the Starting Relay
•
Replace the compressor
•
Reduce the Cooling Load
•
Charge Correct Refrigerant Gas
•
Repair Leakage and Charge Correct Refrigerant Gas
•
Repair or Replace the Strainer
•
Remove the Obstacle
•
Cleaning the Air Filter
•
Take Away the Obstacle
•
Replace the Indoor Fan Motor
•
Take Away any Obstacle
•
Same as Tripped High Pressure Switch Remedy Action
•
Repair or Replace the Strainer
•
Remove the Obstacle
•
Take away the obstacle
•
Replace the Outdoor Fan Motor
•
Take Away any Obstacle
•
Replace the Thermistor(s)
•
Same as Tripped High Pressure Switch Remedy Action