Object
Description
Enter the device name according to the PROFINET rules:
It consists of one or more labels separated by a dot.
The total length is 1 to 240 characters.
Device Name
The length of a label is 1 to 63 characters.
Labels only consist of lower case characters, digits and "-".
The first and the last character of a label must not be "-".
This field is read-only. The IP address is assigned from the PLC. PROFINET IO is not
IP Address
allowed to share the IP address with a CIM 500 webserver.
Subnet Mask
This field is read-only. The subnet mask is assigned from the PLC.
Gateway
This field is read-only. The gateway address is assigned from the PLC.
The module can be put in product simulation mode to generate realistic simulated values
of all the PROFINET IO input data. It is thus possible to connect a PROFINET IO master
to a module fitted in a CIU or an E-box without installing this device in a real industrial
process system. In an office environment, it can then be verified that communication
Grundfos product
works, and data is received and handled correctly by the PROFINET IO master
simulation
application program (for example PLC program) before installing the device.
To enable product simulation, select a product type from the dropdown list.
To terminate product simulation, select "No Simulation".
Press the restart button if LED1 flashes red, which indicates a wrong or missing
Restart
PROFINET IO configuration.