Electrical Wiring
(B) Definition and description of SW03
Manner of set
SW03_1
address
Set the
Communication
SW03_2
and Central
~
control address
SW03_8
with dip switch
(*Note)
Note *:
• Set the address by code when connecting the centralized controller or gateway or charge system.
• Address of centralized controller=communication address+0 or+64.
SW03_ 2=OFF, address of centralized controller=communication address+0=communication address
SW03_ 2=ON, address of centralized controller=communication address+64 (applies when centralized controller is
used and there are more than 64 indoor units)
• To use with 0010451181A in use, it is required to use code for address setting. Set SW03_1=0N
and SW03_ 2=OFF; SW03_3, SW03_ 4, SW03_5, SW03_6, SW03_7 and SW03_ 8 are
according to actual address.
• Address setting function of wired controller for ultrathin card machine is disnabled.
0
Set the address with wired controller or automatism (default)
1
[2]
[3]
[4]
[5]
0
0
0
0
0
0
0
0
0
0
0
0
...
...
...
...
0
1
1
1
1
0
0
0
1
0
0
0
1
0
0
0
...
...
...
...
1
1
1
1
Set the address with dip switch
[6]
[7]
[8]
Address of indoor unit
0
0
0
0# (Default)
0
0
1
0
1
0
...
...
...
1
1
1
0
0
0
0
0
1
0
1
0
...
...
...
1
1
1
17
Address of centralized
controller
0# (Default)
1#
1#
2#
2#
...
...
63#
63#
0#
64#
1#
65#
2#
66#
...
...
63#
127#
address codes which are set