DIPSWITCH P SETTING
OFF
ON
*
Thermostatic temperature control for operation at modulated power
*
Standard adjustement band
*
OFF
1
2
3
4
ON
Motorised louver control
Extended adjustement band
Thermostatic temperature control for 3-level operation
DIPSWITCH CONFIGURATION
Configuration of dipswitches must only be carried out by qualified personnel during unit installation.
Always disconnect the power supply before performing this operation.
Adjust the dipswitches inside the thermostat for the following functions:
Sw 1
Dipswitch 1 (Default OFF)
Thermostatic temperature control:
- for operation at modulated power, set to OFF
- for 3-level operation, set to ON
Dipswitch 2 (Default OFF)
Adjustment band:
- for standard, set to OFF
- for extended, set to ON
Dipswitch 3 (Default OFF)
Louver control:
- for manual control, set to OFF
- for motorised control, set to ON
Dipswitch 4 (Default OFF)
Probe correction:
- for dynamic correction of values, set to OFF
- for fixed correction of values (heating mode 4°C), set to ON
Dipswitch 5 (Default OFF)
Enable heating mode according to water temperature:
- for normal heating mode (39°C), set to OFF
- for reduced Heating (35°C), set to ON
Dipswitch 6 (Default OFF)
Enable cooling mode according to water temperature:
- for normal cooling mode (17°C), set to OFF
- for reduced cooling (22°C), set to ON
Manual louver control
*
Dynamic probe correction of value
*
Normal heating mode (water 39°C)
*
Normal cooling mode (water 17°C)
5
6
Reduced cooling mode (water 22°C)
Reduced heating mode (water 35°C)
Fixed probe correction of value
*
= Factory settings
*
Set up without valve
*
(VCH) Cooling/Heating valve activation
*
OFF
1
2
3
4
ON
Pre-set in factory
Pre-set in factory
Set up with valve
Sw 2
Dip 1 (Default OFF )
Valve set up:
-set up without valve (Y1), OFF
-set up with valve (Y1), ON
Dip 2 (Default OFF )
Valve activation:
-Heating/Cooling valve activation (Y1), OFF
-Preset in factory
Dip 3 (Default OFF)
Preset in factory
Dip 4 (Default OFF)
Preset in factory
IHLLX 2204 - 6887202_04
Pre-set in factory
*
Pre-set in factory
Sw 2
Pre-set in factory
31