2.
ADVICE AND RECOMMENDATIONS.
2.1.
All local regulations, including those referring to national and European standards must be met when
installing the boiler. Including the recommendation guides on biomass installations.
2.2.
In order to prevent the risk of accident, a correct installation must be done following the instructions of this
manual. Your ECOFOREST distributor will be available to help you and provide you information related to
codes, assembly and installation norms in your area.
2.3.
As ECOFOREST do not have direct control on the installation of your boiler, ECOFOREST do not guarantee it
and do not bear the responsibility of any damage that could result from a bad use or a bad installation.
2.4.
We carefully recommend the heat calculation to be made by a qualified heating engineer.
2.5.
The installation and start-up of the device must be carried out by an authorized installer, completing and
submitting the start-up sheet.
2.6.
Maintenance work to be carried out at the end of the season or for every 500 kg of fuel burned, as well as
any repairs or equipment modifications, must be performed by authorized personnel.
2.7.
The boiler must be installed on floors of sufficient bearing capacity and, if the existing construction does not
allow this, the floor must be adapted and made suitable, for example by fitting a load distribution plate.
2.8.
Never use petrol, fuel for lanterns, kerosene nor any similar liquid. Keep this kind of fuel away from your
boiler.
2.9.
Do not try to turn on the boiler if the sight glass is broken.
2.10. Make sure the combustión chamber door of the fireplace is well closed while the boiler is in operation; also
check the cleaning hatches (if you have touched them).
2.11. Unauthorized modifications are forbidden. Use only spare parts provided by Ecoforest (see exploded view).
2.12. Do not overload the boiler; continuous heating efforts might cause premature aging and damage paint (it is
recommended not to exceed 250°C for gas outlet temperature). In biomass systems, the maximum
recommended switching on and off is four per day.
2.13. Do not use the boiler as a burner.
2.14. Consider the configuration of the ANTI-ICING and ANTI-LOCK menus (see user manual). If the boiler is not
being used over long periods of time and there is a risk of it freezing, empty the device to avoid breakage.
2.15. To prevent possible electrical shocks, only trained personnel should have access to the sides and the back of
the boiler.
2.16. The hydraulic circuit must always keep open a dissipation circuit greater than 30% of the total installation.
2.17. It is highly advisable to perform regular checks to assess the quality of the water in the system, especially if
more water is being added. If you use a water treatment product, make sure it is compatible with the
materials used in the heating installation. To do so, please contact the product's manufacturer.
2.18. In order to refill the boiler with fuel, the user must open the hopper lid and empty the contents of the fuel
tank carefully, to prevent it from overflowing. Do not open the hopper during operation of the machine.
Hopper lid.
Fuel.
If the fuel loading system is pneumatic, remember to follow the steps in the pneumatic feeder manual.
Ecoforest only guarantees the operation with our pneumatic feeder. In the event of installing one of another brand,
it must be ensured that the system does not load the boiler hopper during boiler operation, that is, the boiler must
41
Drawing 1