tau K130MA Guía Para La Instalación página 21

Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

4 - 6
OPEN/CLOSE
5 - 6
STOP
INTERNAL
7 - 8
PHOTOCELLS
EXTERNAL
7 - 9
PHOTOCELLS
SENSITIVE
7 - 10
EDGE
11 - 12
PHOTOCELLS
12 - 13
TX PHOTOCELLS
FLASHING
14 - 15
LIGHT
GATE OPEN
16 - 17
LIGHT
COURTESY
16 - 18
LIGHT
19 - 20
2
CH RADIO
nd
OPEN/CLOSE button N.O. input – Controls the opening and closing of the
automation and is regulated based on the function of dip-switches 2 and
4. (4= O/C - 6= COM)
STOP button N.C. input – Stops the automation in any position, temporarily pre-
venting the automatic closure, if programmed. (5= STOP - 6= COM )
NOTE: A safety micro-switch is connected to the STOP push-button. In case
the STOP input remains open for more than 5 seconds, the operator will per-
form a cycle at a slow speed to reset the operating parameters to the values
originally saved (see "Restoring automatic operation"). The micro-switch
should be connected in series to further STOP push-buttons where present.
PHOTOCELL OR SAFETY DEVICE input INSIDE the gate (Normally Closed con-
tact). When these devices trigger during the opening phase, they temporarily
stop the gate until the obstacle has been removed; during the closing phase
they stop the gate and then totally open it again. Bridge the connectors if
not used. (7= COM - 8= CLOSE)
PHOTOCELL OR SAFETY DEVICE input OUTSIDE the gate (Normally Closed
contact). Then these devices trigger during the closing phase, they stop the
gate and then totally open it again. Bridge the connectors if not used. (7=
COM - 9= FOT)
Note: the photocell transmitter must always be supplied by terminals
no. 12 and no. 13, since the safety system test (phototest) is carried
out on it. Without this connection, the control unit does not work. To
override the testing of the safety system, or when the photocells are
not used, set dip-switch no. 6 to OFF.
SAFETY EDGE input (Resistive sensitive edge or with n.c. contact - see DIP
SWITCH 12 ). It works during the opening phase and also during the closing phase,
resulting in the temporary stop of the automation and:
- the partial inversion of its movement for 20 cm (only in the opening phase)
- the complete opening (only in the closing phase);
thus freeing any obstacle. NOTE: if a resistive sensitive edge is connected,
set dip-switch no. 12 to ON;
If a fixed safety edge with NC contact is connected, set dip-switch no.
12 to OFF;
Jumper terminals if not used. (7= COMMON - 10= SENSITIVE EDGE)
18/24 V
output
DC max. 15 W per photocells (TX/RX) and auxiliaries
(11 = NEGATIVE - 12 = POSITIVE)
output for the 18/24 V DC transmitter photocell with the possibility of
carrying out the phototest (with DIP 6 ON). (12= POSITIVE - 13= NEGATIVE)
18/24 V
DC max. 20W output for flashing light supply, flashing signal sup-
plied by the control unit, rapid for closing, slow for opening.
(14= POSITIVE - 15= NEGATIVE)
Output for OPEN GATE LIGHT
the light flashes slowly, when the bar is open it stays on and while closing
it flashes at twice the speed. (16= POSITIVE - 17= NEGATIVE)
18/24 V
DC, 15 W Output for auxiliary courtesy light. It comes on with the
control pulse and stays ON until after the manoeuvre for a time settable
through TauApp (default = 20 sec.) (16=POSITIVE - 18= NEGATIVE)
2
radio channel output - for control of an additional automation or for
nd
switching on lights, etc... (N.O. clean contact)
Warning: to connect other devices to the 2nd Radio Channel (area
lighting, pumps, etc.), use an additional auxiliary relay (see note at
end of paragraph).
WARNING: the default outlet is active monostable 2 sec. To switch it
to active bistable or to modify the activation time it is necessary to
use the T-WIFI.
18/24 V
DC, 3 W max; while the bar opens
21

Publicidad

Tabla de contenido
loading

Tabla de contenido