KAL710 Addressable Conventional Zone Module
Installation Sheet
EN ES
IT
PT FR NL CS NO PL HU
1
EN: Installation Sheet
Description
The KAL710 Addressable Conventional Zone Module is used
to connect one conventional fire zone to an addressable fire
system loop.
The module may be used in detection systems with no area
subdivision and/or when exact location data is not required.
One module may be used to connect up to 20 conventional
detectors and an unlimited number of manual call points or
normally open (NO) contacts to the fire detection system.
Installation
Caution:
For general guidelines on system planning, design,
installation, commissioning, use and maintenance, refer to the
EN 54:14 standard and local regulations.
© 2021 Carrier. All rights reserved.
Module Installation
Disconnect the fire system power supply and install the module
in the protective housing provided.
Connect the loop cable shield wire to the earth screw and
install a 4.7 kΩ end-of-line resistor at the end of the detection
zone.
The 24 V power supply for the module must be provided by an
auxiliary power source.
Connection
The module connectors, DIP switch, and status LED are
shown in Figure 1:
1.
Earth screw
2.
Loop connectors
3.
Auxiliary power supply connectors
4.
Zone output connectors
5.
DIP switch
6.
Status LED
1 / 16
P/N 10-5151-501-102-02 • ISS 08JUN21