Descargar Imprimir esta página

Vortice PHANTOM BP Manual De Instrucciones página 40

Ocultar thumbs Ver también para PHANTOM BP:

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 93
ENGLISH
Installer "Operations menu" page
Enter the password as shown in the figure to access the installer "Oper ations menu."
MAIN MENU
USE MENU
ALARM
SETUP
INFO
From this new page you can manage:
• Setp Byp.
"By-pass" function activ ation depends on the
temperature. "Setp Byp" is selectab le into a v ariable r ange
between: 15°C & 30°C (default value = 18°C).
• Lifetime
Is shown the duration of Filters Pre-Alar m.
(See "Pre -alarm: Filters checking"):
- after 3 or 6 or 12 months;
• Reset Fil
In case of Filters replacing, y ou need to reset the Filters Timer
manually:
- select [YES] to reset;
- select [NO] to not resect.
• Modbus ID
In the presence of another HMI user interf
remote, you can configure an address other than that set b y
default which is "160" (f
12107). (page 39)
• Speed
See Fig. 3
From "Installer menu" page, selecting "Speed", you can join to
"Setting speed". Here, you can set motorfan speeds:
(C) Clean air outlet inside the room;
(D) Stale air outlet to outside .
For more details on setting "Speed", See:
"Setting Speed Menu"
40
ace installed in
or code 12106) or "1" (f
PASSWORD
023
"Setp Byp"
or code
SETP BYP.
LIFE TIME
RESET FIL
MBUS ID
SPEED
LANGUAGE
NO FROST
QUIET
QUIET PR.
SETP BYP.
018
LIFE TIME
003
RESET FIL
YES
MODBUS ID
160
SPEED
VSUP1
Å
VEXH1
VSUP2
VEXH2
VSUP3
VEXH3
VSUP B
VEXH B
TECHNIC.
[ ▲ ]
[ ▲ ]
[ ▲ ]
[ ▲ ]
[ ▲ ]

Publicidad

loading

Este manual también es adecuado para:

Phantom bp h