Descargar Imprimir esta página

Eaton DIN500AC Guia Del Usuario página 16

Ocultar thumbs Ver también para DIN500AC:

Publicidad

Idiomas disponibles

Idiomas disponibles

Remote ON /Off Terminals
The remote ON/OFF is grounded to the UPS internal signal ground and should be isolated from the chassis
ground to prevent any ground potentials that may cause a unit malfunction or damage. In addition, isolate the
Remote ON/OFF wiring away from high current, high voltage, and high frequency components to prevent any
magnetically-coupled noise on the Remote On/Off connections.
Table 2. Remote ON / OFF Wire Specifications
Wire Strip Length
Screw Torque
Screw Size
Preferred AWG
Table 3. Remote Enable/Disable of UPS
AC DIN RAIL UPS Remote ON/OFF Switch
Wired
UPS (NC)
UPS (NO)
No external voltage is required. We recommend using stranded UTP (Unshielded Twisted Pair) wire for connections.
Eaton Din Rail UPS Advanced User Guide 9340AC—Rev A
12
0.35 in. (0.9 cm )
5.3 lb-in (60 N-cm)
M3.0
18 AWG for DIN500AC
14 AWG for DIN850AC
To Enable the UPS, close the switch connected to the terminals.
To Disable the UPS, open the switch connected to the terminals.
UPS Condition/ State
ON
OFF
Remote ON/OFF Terminals: Shorted (closed) for ON, Open for OFF Non- Polarized terminals.
Switch or Terminal Condition

Publicidad

loading

Este manual también es adecuado para:

Din850ac