AL3 Group - alarm 3 parameters
Param Description
Liv N°
44
AL3t
Alarm 3 type
LbA Group - Loop break alarm
Liv N°
Param Descrizione
C
52
LbAt
LBA time
rEG Group - Control parameters
Param Description
Liv N°
C
56
cont
Control type
C
57
Auto
Autotuning selection
C
58
tunE
Manual start of the Autotuning
M12927CA
Values
nonE = Alarm not used
LoAb = Absolute low alarm
HiAb = Absolute high alarm
LHAo = Windows alarm in alarm outside the
windows
LHAI = Windows alarm in alarm inside the
windows
SE.br = Sensor Break
LodE = Deviation low alarm (relative)
HidE = Deviation high alarm (relative)
LHdo = Relative band alarm in alarm out of the
band
LHdi = Relative band alarm in alarm inside the
band
Values
Da 0 (oFF) a 9999 (s)
Values
Pid = PID (heat and/or)
On.FA = ON/OFF asymmetric hysteresis
On.FS = ON/OFF symmetric hysteresis
nr = Heat/Cool ON/OFF control with neutral zone
3Pt = Servomotor control (available only when
Output 2 and
Output 3 have been ordered as "M")
-4 = Oscillating auto-tune with automaticrestart at
power up and after all point change
-3 = Oscillating auto-tune with manual start
-2 = Oscillating -tune with auto-matic start at the
first power up only
-1 = Oscillating auto-tune with auto-matic restart
at every power up
0 = Not used
1 = Fast auto tuning with automatic restart at
every power up
2 = Fast auto-tune with automatic start the first
power up only
3 = FAST auto-tune with manual start
4 = FAST auto-tune with automatic restart at
power up and
after set point change
5 = Evo-tune with automatic restart at every
power up
6 = Evo-tune with automatic start the first power
up only
7 = Evo-tune with manual start
8 = Evo-tune with automatic restart at power up
and after a set point change
oFF = Not active
on = Active
11
Default
nonE
Default
oFF
Default
3pt
7
oFF