ConF > OutP (parameter under group only for RWF50.3)
Parameter
FnCt
tipo di controllo
SiGn
type of output signal
rOut
Value when out of
input range
oPnt
zero point
End
End value
(bold = factory settings)
ConF > binF
Parameter
bin1
digital inputs
(terminals DG - D1)
(bold = factory settings)
ConF > dISP
Parameter
diSU
upper display
(red)
diSL
lower display
(green)
tout
timeout
dECP
decimal point
CodE
level lockout
(bold = factory settings)
Value
1
4
0
1
2
0...101
-1999...0..+9999
-1999...100..+9999
Value
0
1
2
4
Value
0
1
4
6
7
0
1
4
6
7
0..180..250
0
1
2
0
1
2
3
Description
1 = analog input 1 doubling with possibility to convert
(depending on par SiGn)
4 = modulation controller
physical output signal (terminals A+, A-)
0 = 0÷20mA
1 = 4÷20mA
2 = 0÷10V
signal (in percent) when measurement range is crossed
value range of the output variable is assigned to a physical
output signal Per default, the setting corresponds to 0...100%
angular positioning for the controller outputs (terminals A+, A-)
(effective only with FnCt = 1)
value range of the output variable is assigned to a physical
output signal Per default, the setting corresponds to 0...100%
angular positioning for the controller outputs (terminals A+, A-)
(effective only with FnCt = 1)
Description
0 = without function
1 = set-point changeover (SP1 / SP2)
2 = set-point shift (Opr > dSP parameter = value of set-point
modify)
4 = changeover of operating mode
open – modulating operation;
close – 2 stage operation.
Description
display value for upper display:
0 = display power-off
1 = analog input value
4 = Controller's angular positioning
6 = set-point value
7 = end value with thermal shock protection
display value for lower display:
0 = display power-off
1 = analog input value
4 = Controller's angular positioning
6 = set-point value
7 = end value with thermal shock protection
time (s) on completion of which the controller returns
automatically to the basic display, if no button is pressed
0 = no decimal place
1 = one decimal place
2 = two decimal places
0 = no lockout
1 = configuration level lockout (ConF)
2 = Parameter and configuration level lockout (PArA & ConF)
3 = keyboard lockout
7